5925-00-074-4226

CIRCUIT BREAKER


5925-00-074-4226 (5925000744226, 000744226)
Part Number (1 listing): 3XAM1516MG3-10-380AC
Summary

FSG 59 / FSC 5925

DEMIL: A

DEMIL INT: 1

HMIC: P

Date Created: 1 Jan 1961

MSDS: None

Hazmat: None

Request a Quote


;



MASTER CROSS REFERENCE LIST (MCRL) | NSN 5925-00-074-4226 Submit RFQ
Manufacturer Part NumberRNCCRNVCManufacturer NameCAGE
3XAM1516MG3-10-380AC3 - Design Control Reference9 - No Longer UsedEATON CORP  74193    CAGE 74193  
Code Definitions

3 - Design Control Reference

Reference Number Category Code (DRN_2910)


Design Control Reference. The primary number used to identify an item of production or a range of items of production, by the manufacturer (individual, company, firm, corporation, or Government activity) which controls the design, characteristics, and production of the item by means of its engineering drawings, specifications and inspection requirements.

9 - No Longer Used

Reference Number Variation Code (DRN_4780)


A specification, standard, or other reference number which is superseded, canceled, obsolete or discontinued and is coded Reference Number Category Code (RNCC) 5; a reference number for information only coded RNCC 6; or a reference number coded RNCC D.


FLIS - SEG A - IDENTIFICATION | NSN 5925-00-074-4226 Submit RFQ
FSGFSCNIINFIIGINCCRITICALITYTYPE OF ITEMMRCDEMILHMICEDCPMICADPECDATE CREATED
595925000744226A030A000136X1APU1 Jan 1961
Code Definitions

59

Federal Supply Group (FSG_3994/FSC_WI_FSG_3996)


Electrical and Electronic Equipment Components

5925

Federal Supply Class (FSC_3994/FSC_WI_FSC_3996)


Circuit Breakers

000744226

National Item Identification Number (NCB_CD_4130/I_I_NBR_4131)


NSN 5925-00-074-4226

A030A0

Federal Item Identification Guide (FIIG_4065)

00136

Item Naming Code (INC_4080)

1 Jan 1961

NIIN Assignment Date (DT_NIIN_ASGMT_2180)

X

Item Criticality (CRITL_CD_FIIG_3843)


The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.

1

Type of Item Identification (TYP_II_4820)


Full Descriptive Item Identification

A

Demilitarization Code (DEMIL_CD_0167)


Non-MLI/ Non-SLI — Demilitarization not required.

P

Hazardous Material Indicator Code (HMIC_0865)


Indicates there is no information in the HMIRS; however, the NSN is in a FSC in Table II of Federal Standard 313 and a MSDS may be required by the user. The requirement for a MSDS is dependent on a hazard determination of the supplier or the intended end use of the product.

U

Precious Metals Indicator Code (PMIC_0802)


Precious Metal Content is unknown.


FLIS - SEG B - MOE RULE DATA | NSN 5925-00-074-4226 Submit RFQ
MOE RuleFormer MOEAMCAMSCNIMSCIMCIMC ActivityAACDSORCollaboratorsReceiversEffective Date
ZR011 Apr 1991
Code Definitions

FLIS - SEG C - REFERENCE NUMBER | NSN 5925-00-074-4226 Submit RFQ
RNFCRNCCRNVCDACRNAACRNSCRNJCSADCMSDSHCCReference NumberCAGE
339ETXD3XAM1516MG3-10-380AC  74193   CAGE/74193
Code Definitions

3

Reference Number Format Code (RNFC_2920)


Number format is unknown. (Coded RNFC 3 by the Defense Logistics Information Service upon implementation of FLIS.)

3

Reference Number Category Code (RNCC_2910)


Design Control Reference. The primary number used to identify an item of production or a range of items of production, by the manufacturer (individual, company, firm, corporation, or Government activity) which controls the design, characteristics, and production of the item by means of its engineering drawings, specifications and inspection requirements.

9

Reference Number Variation Code (RNVC_4780)


A specification, standard, or other reference number which is superseded, canceled, obsolete or discontinued and is coded Reference Number Category Code (RNCC) 5; a reference number for information only coded RNCC 6; or a reference number coded RNCC D.

E

Document Availability Code (DAC_2640)


The reference number is represented by engineering data other than an engineering drawing. The data is available for unlimited use and will be furnished by the activity identified by the RNAAC upon request.

TX

Reference Number Action Activity Code (RNAAC_2900)


Defense Supply Center Columbus, Columbus, OH 43218

D

Reference Number Status Code (RNSC_2923)


Procurement authority of the manufacturer and reference number have not yet been checked. NOTE: This code is to be allocated to reference numbers still requiring checks on procurement authority.


FLIS - SEG E - ITEM STANDARDIZATION DATA | NSN 5925-00-074-4226 Submit RFQ
ISCOriginatorNIIN StatusReplaced / Replacement ISCReplaced / Replacement OriginatorReplacement NIIN StatusReplacement DateReplaced / Replacement NSNDecision Date
CTX06 Sep 1971
Code Definitions

C

Item Standardization Code (ISC_2650)


An item authorized for procurement that has been included in an item reduction study but an intelligent decision could not be made due to lack of sufficient technical data.

TX

Originator of Standardization Decision (ORG_STDZN_DEC_9325)


Defense Supply Center Columbus, Columbus, OH 43218

0

NIIN Status Code (NIIN_STAT_CD_2670)


Item is active. File data coded KFD is forwarded. if this KFD data represents your item of supply, submit, if applicable, an LAD, LAU, or LCU transaction. Otherwise, use the National Stock Number (NSN) in your supply system.

6 Sep 1971

Standardization Decision Date (DT_STDZN_DEC_2300)


FLIS - SEG G - FREIGHT DATA | NSN 5925-00-074-4226 Submit RFQ
IntegrityOriginatingHMCLCLWCCTCCSHCADCACCASHLTLNMFCNMFC Sub ItemUFCFreight DescriptionRail Variance
P658Z9AHZP061300X34410CIRCUIT-BREAKER-SWITCH-NOI
Code Definitions

XX

Originating Activity Code (ORIG_ACTY_CD_4210)


P

Less Than Carload (LCL_CD_2760)


77.5

658

Water Commodity Code (WRT_CMDTY_CD_9275)


Electical Appliances, Small

Z

Type Cargo Code (TYPE_CGO_CD_9260)


No special type of cargo code applicable

9

Special Handling Code (SP_HDLG_CD_9240)


No special handling required

A

Air Dimension Code (AIR_DIM_CD_9220)


Shipment is not a consolidation and does not exceed 72 inches in any dimension.

H

Air Commodity Code (AIR_CMTY_HDLG_9215)


Signal Corps supplies and equipment, including radio equipment and supplies, communications equipment and supplies, electrical equipment and supplies, etc.

Z

Air Special Handling Code (AIR_CMTY_HDLG_9215)


No special handling required.

061300

National Motor Freight Classification Number (NMFC Item Number) (NMFC_2850)

X

NMFC Sub Item Number (SUB_ITM_NBR_0861)

34410

Uniform Freight Classification (UFC_CD_MODF_3040)

CIRCUIT-BREAKER-SWITCH-NOI

Freight Description (FRT_DESC_4020)

Rail Variance

Rail Variance (RAIL_VARI_CD_4760)


No Variation. NMFC and UFCC Match.


FLIS - SEG M/V - CHARACTERISTICS DATA | NSN 5925-00-074-4226 Submit RFQ
MRCDecoded RequirementClear Text Reply
CPRWActuator FunctionTRIP-RESET
CPRXActuator Position DesignationAT EACH POLE
APNQArc Quenching MethodMAGNETIC BLOWOUT
ADAQBody Length3.709 INCHES MINIMUM AND 3.729 INCHES MAXIMUM
AAQLBody StyleMULTIPOLE-MULTIPLE ACTUATOR TYPE
ADATBody Width3.042 INCHES MINIMUM AND 3.062 INCHES MAXIMUM
AJECBoss Height0.146 INCHES MINIMUM AND 0.166 INCHES MAXIMUM
ADTVCase MaterialPLASTIC
AEBPCenter To Center Distance Between Terminals Parallel To Length3.053 INCHES MINIMUM AND 3.073 INCHES MAXIMUM
AEBQCenter To Center Distance Between Terminals Parallel To Width1.021 INCHES MINIMUM AND 1.041 INCHES MAXIMUM
CPRHCircuit Protection TypeOVERCURRENT ALL LOCATIONS
AEBYDistance Between Centerlines Of Mounting Facilities Parallel To Body Length2.740 INCHES MINIMUM AND 2.760 INCHES MAXIMUM
AEHADistance Between Centerlines Of Mounting Facilities Parallel To Body Width1.021 INCHES MINIMUM AND 1.041 INCHES MAXIMUM
CPRYExternal Actuator Linkage ArrangementONE, TWO, AND THREE LINKED
AFJNFragility FactorMODERATELY RUGGED
FREQFrequency In Hertz400.0 ALL LOCATIONS
CPLMMaximum Continuous Load Current Rating Per Pole10.0 AMPERES AC ALL LOCATIONS
CPRGMaximum Interrupting Capacity Current Type And Rating Per Pole In Amps1500.0 AC ALL LOCATIONS
AXHRMounting Facility Type And Quantity6 THREADED HOLE
AJWXMounting Surface To Terminal End Distance3.239 INCHES NOMINAL
CQJXNominal Thread Size0.138 INCHES
CPRFOperating Voltage Type And Rating Per Pole In Volts380.0 AC ALL LOCATIONS
CQXFInclosure Protection Type For Which DesignedDUSTPROOF AND FUNGUS PROOF
CPSMInternal Trip Release ConfigurationSERIES TRIP ALL LOCATIONS
CPRRMain Contact Tripping Mechanism TypeTRIP FREE
CPRTManual Actuator Type And Quantity3 TOGGLE
AKPXPole Quantity3
CPRQReset MethodMANUAL
CQWNTrip Delay Time In Seconds Per Rated Continuous Current40.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 105.000 MAXIMUM AT 200 PCT ALL LOCATIONS
CPRLTrip Release CharacteristicTIME DELAY ALL LOCATIONS
CPRJTrip Release MethodMAGNETIC-HYDRAULIC ALL LOCATIONS
CPRNUltimate Trip Rating Of Continuous Current Rating Per Pole In Percent150.0 ALL LOCATIONS
BBRGStorage TypeGENERAL PURPOSE WAREHOUSE
TTQYTerminal Type And Quantity6 THREADED STUD
CMLPThread Quantity Per Inch32
THSDThread Series DesignatorUNC


Back to Top
Back to Top