Manufacturer Part Number | RNCC | RNVC | Manufacturer Name | CAGE | |
---|---|---|---|---|---|
NFJ631020R | 3 - Design Control Reference | 9 - No Longer Used | CHALLENGER ACQUISITION CORP | 02201 | ![]() |
NFJ631020R | 5 - Replaced / Discontinued | 9 - No Longer Used | FEDERAL PACIFIC ELECTRIC CO | 79443 | ![]() |
Design Control Reference. The primary number used to identify an item of production or a range of items of production, by the manufacturer (individual, company, firm, corporation, or Government activity) which controls the design, characteristics, and production of the item by means of its engineering drawings, specifications and inspection requirements.
Secondary Reference. Any additional number, other than a primary number (codes 1,2,3,4) informative reference (code 6) or vendor item drawing reference (code 7) assigned to an item of production or supply by a commercial or Government organization, which represents the same item of production or supply to which the National Stock Number (NSN) was assigned. The reference number may have had an RNCC of 1, 2, 3, 4 or 7 but has since been replaced in the item-of-supply concept of the NSN by another primary number.
A specification, standard, or other reference number which is superseded, canceled, obsolete or discontinued and is coded Reference Number Category Code (RNCC) 5; a reference number for information only coded RNCC 6; or a reference number coded RNCC D.
FSG | FSC | NIIN | FIIG | INC | CRITICALITY | TYPE OF ITEM | MRC | DEMIL | HMIC | EDC | PMIC | ADPEC | DATE CREATED |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
59 | 5925 | 000879944 | A030A0 | 00136 | X | 1 | A | P | A | 1 Jan 1961 |
The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.
Full Descriptive Item Identification
Non-MLI/ Non-SLI — Demilitarization not required.
Indicates there is no information in the HMIRS; however, the NSN is in a FSC in Table II of Federal Standard 313 and a MSDS may be required by the user. The requirement for a MSDS is dependent on a hazard determination of the supplier or the intended end use of the product.
Item does not contain Precious Metal.
MOE Rule | Former MOE | AMC | AMSC | NIMSC | IMC | IMC Activity | AAC | DSOR | Collaborators | Receivers | Effective Date | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
ZW01 | 1 Nov 2005 |
RNFC | RNCC | RNVC | DAC | RNAAC | RNSC | RNJC | SADC | MSDS | HCC | Reference Number | CAGE | |
---|---|---|---|---|---|---|---|---|---|---|---|---|
3 | 3 | 9 | E | TX | D | NFJ631020R | 02201 | ![]() | ||||
3 | 5 | 9 | E | TX | B | NFJ631020R | 79443 | ![]() |
Number format is unknown. (Coded RNFC 3 by the Defense Logistics Information Service upon implementation of FLIS.)
Design Control Reference. The primary number used to identify an item of production or a range of items of production, by the manufacturer (individual, company, firm, corporation, or Government activity) which controls the design, characteristics, and production of the item by means of its engineering drawings, specifications and inspection requirements.
A specification, standard, or other reference number which is superseded, canceled, obsolete or discontinued and is coded Reference Number Category Code (RNCC) 5; a reference number for information only coded RNCC 6; or a reference number coded RNCC D.
The reference number is represented by engineering data other than an engineering drawing. The data is available for unlimited use and will be furnished by the activity identified by the RNAAC upon request.
Defense Supply Center Columbus, Columbus, OH 43218
Procurement authority of the manufacturer and reference number have not yet been checked. NOTE: This code is to be allocated to reference numbers still requiring checks on procurement authority.
Secondary Reference. Any additional number, other than a primary number (codes 1,2,3,4) informative reference (code 6) or vendor item drawing reference (code 7) assigned to an item of production or supply by a commercial or Government organization, which represents the same item of production or supply to which the National Stock Number (NSN) was assigned. The reference number may have had an RNCC of 1, 2, 3, 4 or 7 but has since been replaced in the item-of-supply concept of the NSN by another primary number.
Manufacturer and/or reference number are not authorized for procurement. NOTE: This code may be used for obsolete or informative reference numbers only.
ISC | Originator | NIIN Status | Replaced / Replacement ISC | Replaced / Replacement Originator | Replacement NIIN Status | Replacement Date | Replaced / Replacement NSN | Decision Date |
---|---|---|---|---|---|---|---|---|
2 | TX | 0 | 21 Oct 1967 |
An item authorized for procurement which has been included in an item reduction study and which initially does not replace an item not authorized for procurement. In addition, in generic relationships, a code 2 item is related to a code 1 item.
Defense Supply Center Columbus, Columbus, OH 43218
Item is active. File data coded KFD is forwarded. if this KFD data represents your item of supply, submit, if applicable, an LAD, LAU, or LCU transaction. Otherwise, use the National Stock Number (NSN) in your supply system.
Integrity | Originating | HMC | LCL | WCC | TCC | SHC | ADC | ACC | ASH | LTL | NMFC | NMFC Sub Item | UFC | Freight Description | Rail Variance |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
658 | Z | 9 | A | H | Z | P | 061300 | X | 34410 | CIRCUIT-BREAKER-SWITCH-NOI |
Electical Appliances, Small
No special type of cargo code applicable
No special handling required
Shipment is not a consolidation and does not exceed 72 inches in any dimension.
Signal Corps supplies and equipment, including radio equipment and supplies, communications equipment and supplies, electrical equipment and supplies, etc.
No special handling required.
77.5
No Variation. NMFC and UFCC Match.
Source | PICA / SICA | Packaging Category | Storage | Preservation | Clean/Dry | INT Qty | Unit Weight | Unit Size | Unit Pack Cube | Item Weight | Item Dims |
---|---|---|---|---|---|---|---|---|---|---|---|
M | P | 1 | AAA | 8.0 lbs | 0.289 cu ft |
Preservation Material | Wrapping Material | Cushioning / Dunnage | Cushioning Thickness | Unit Container | Intermediate Container | Unit Container Level | Special Marking | Level A Packing | Level B Packing | Minimal Packing | Optional Procedure |
---|---|---|---|---|---|---|---|---|---|---|---|
00 | FA | X | DO | 00 | E | Q | U |
Manufacturer/Contractor (This code is restricted to DLA LOGISTICS INFORMATION SERVICE input only.)
Primary Inventory Control Activity (PICA)
Any suitable process that is not injurious to the item.
No requirement
MIL-P-130, laminated and creped wrapping paper
As required to protect the item or elements of the package
Any suitable fiber box included in this table may be used (see J.4.9.1).
No special marking
Packing shall be accomplished to meet the performance test requirements of ASTMD4169, Distribution Cycle 18, Assurance Level 1.
Packing shall be accomplished in accordance with table C-II for the packing level specified. Closure sealing and reinforcement shall be in accordance with the appropriate shipping container specification.
Items or packages that require packing for acceptance by the carrier shall be packed in exterior type shipping containers in a manner that will ensure safe transportation at the lowest rate to the point of delivery and shall meet, as a minimum, the requirements of the following rules and regulations, as applicable to the mode(s) of transportation to be utilized: (a) Postal Regulations (b) Department of Transportation Regulations (c) Civil Air Regulations (d) Uniform Freight Classification Rules (e) National Motor Freight Classification Rules (f) American Truckers' Association Rules (g) Other applicable carriers' rules (h) Military Air Regulations for dangerous materials Consolidation of Shipments. All exterior packs of 1.5 cubic feet or less having no single dimension (length, width, height) exceeding 40 inches (and when the total number of such containers in any individual shipment exceeds 25), shall be consolidated, using flat pallets, box pallets, or containers as the consolidating media. Dangerous goods shall be prepared for shipment according to applicable Department of Transportation (DOT) regulations and international regulations in effect at time of shipment. Shipments by parcel post must comply with Postal Regulations.
MRC | Decoded Requirement | Clear Text Reply |
---|---|---|
CPRW | Actuator Function | TRIP-RESET |
CPRX | Actuator Position Designation | AT POLE ONE |
ADAU | Body Height | 3.812 INCHES NOMINAL |
ADAQ | Body Length | 9.500 INCHES NOMINAL |
AAQL | Body Style | MULTIPOLE-SINGLE ACTUATOR TYPE |
ADAT | Body Width | 4.125 INCHES NOMINAL |
AJEC | Boss Height | 0.250 INCHES NOMINAL |
ADTV | Case Material | PLASTIC |
AEBP | Center To Center Distance Between Terminals Parallel To Length | 8.000 INCHES NOMINAL |
AEBQ | Center To Center Distance Between Terminals Parallel To Width | 1.375 INCHES NOMINAL |
CPRH | Circuit Protection Type | OVERCURRENT ALL LOCATIONS |
AEBY | Distance Between Centerlines Of Mounting Facilities Parallel To Body Length | 7.250 INCHES NOMINAL |
AEHA | Distance Between Centerlines Of Mounting Facilities Parallel To Body Width | 1.375 INCHES NOMINAL |
AFJN | Fragility Factor | MODERATELY RUGGED |
FREQ | Frequency In Hertz | 60.0 ALL LOCATIONS |
CPLM | Maximum Continuous Load Current Rating Per Pole | 20.0 AMPERES AC ALL LOCATIONS |
CPRG | Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps | 15000.0 AC ALL LOCATIONS |
AXHR | Mounting Facility Type And Quantity | 4 UNTHREADED HOLE |
CPRF | Operating Voltage Type And Rating Per Pole In Volts | 600.0 AC ALL LOCATIONS |
CQXF | Inclosure Protection Type For Which Designed | FUNGUS RESISTANT |
CPSM | Internal Trip Release Configuration | SERIES TRIP ALL LOCATIONS |
CPRR | Main Contact Tripping Mechanism Type | TRIP FREE |
CPRT | Manual Actuator Type And Quantity | 1 ROTARY |
AKPX | Pole Quantity | 3 |
CPRQ | Reset Method | MANUAL |
CQWN | Trip Delay Time In Seconds Per Rated Continuous Current | 28.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 65.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CRCF | Trip Release Ambient Temp Rating | 25.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
CPRL | Trip Release Characteristic | TIME DELAY ALL LOCATIONS |
CPRJ | Trip Release Method | THERMAL ALL LOCATIONS |
CPRN | Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent | 120.0 ALL LOCATIONS |
AEBV | Unthreaded Mounting Hole Diameter | 0.219 INCHES NOMINAL |
BBRG | Storage Type | GENERAL PURPOSE WAREHOUSE |
TTQY | Terminal Type And Quantity | 6 COMPRESSION |