Manufacturer Part Number | RNCC | RNVC | Manufacturer Name | CAGE | |
---|---|---|---|---|---|
AM333-20-250-4-60 | 3 - Design Control Reference | 9 - No Longer Used | EATON CORP | 74193 | ![]() |
Design Control Reference. The primary number used to identify an item of production or a range of items of production, by the manufacturer (individual, company, firm, corporation, or Government activity) which controls the design, characteristics, and production of the item by means of its engineering drawings, specifications and inspection requirements.
A specification, standard, or other reference number which is superseded, canceled, obsolete or discontinued and is coded Reference Number Category Code (RNCC) 5; a reference number for information only coded RNCC 6; or a reference number coded RNCC D.
FSG | FSC | NIIN | FIIG | INC | CRITICALITY | TYPE OF ITEM | MRC | DEMIL | HMIC | EDC | PMIC | ADPEC | DATE CREATED |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
59 | 5925 | 002337520 | A030A0 | 00136 | X | 1 | A | P | U | 10 Mar 1971 |
The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.
Full Descriptive Item Identification
Non-MLI/ Non-SLI — Demilitarization not required.
Indicates there is no information in the HMIRS; however, the NSN is in a FSC in Table II of Federal Standard 313 and a MSDS may be required by the user. The requirement for a MSDS is dependent on a hazard determination of the supplier or the intended end use of the product.
Precious Metal Content is unknown.
MOE Rule | Former MOE | AMC | AMSC | NIMSC | IMC | IMC Activity | AAC | DSOR | Collaborators | Receivers | Effective Date | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
G070 | 0 | 0 | L | 1 Apr 1991 |
Not Established
LOCAL PURCHASE (NON-STOCKED ITEMS) Defense Logistics Agency (DLA)/GSA/Service/Agency-managed items authorized for local purchase as normal means of support at base, post, camp or station level. Item not stocked in wholesale distribution system of IMM/Service/Agency ICP.
RNFC | RNCC | RNVC | DAC | RNAAC | RNSC | RNJC | SADC | MSDS | HCC | Reference Number | CAGE | |
---|---|---|---|---|---|---|---|---|---|---|---|---|
3 | 3 | 9 | E | 75 | D | AM333-20-250-4-60 | 74193 | ![]() |
Number format is unknown. (Coded RNFC 3 by the Defense Logistics Information Service upon implementation of FLIS.)
Design Control Reference. The primary number used to identify an item of production or a range of items of production, by the manufacturer (individual, company, firm, corporation, or Government activity) which controls the design, characteristics, and production of the item by means of its engineering drawings, specifications and inspection requirements.
A specification, standard, or other reference number which is superseded, canceled, obsolete or discontinued and is coded Reference Number Category Code (RNCC) 5; a reference number for information only coded RNCC 6; or a reference number coded RNCC D.
The reference number is represented by engineering data other than an engineering drawing. The data is available for unlimited use and will be furnished by the activity identified by the RNAAC upon request.
GSA, FSS/FCSC Washington, DC 20406
Procurement authority of the manufacturer and reference number have not yet been checked. NOTE: This code is to be allocated to reference numbers still requiring checks on procurement authority.
ISC | Originator | NIIN Status | Replaced / Replacement ISC | Replaced / Replacement Originator | Replacement NIIN Status | Replacement Date | Replaced / Replacement NSN | Decision Date |
---|---|---|---|---|---|---|---|---|
E | TX | 0 | B | TX | 0 | 10 Mar 1973 | 5925001854020 | 18 Jun 1973 |
An item no longer authorized for procurement which has been replaced by an item contained in a new or revised superseding specification or standard.
Defense Supply Center Columbus, Columbus, OH 43218
Item is active. File data coded KFD is forwarded. if this KFD data represents your item of supply, submit, if applicable, an LAD, LAU, or LCU transaction. Otherwise, use the National Stock Number (NSN) in your supply system.
A new item authorized for procurement, contained in a new or revised superseding specification or standard, that replaces prior items.
Integrity | Originating | HMC | LCL | WCC | TCC | SHC | ADC | ACC | ASH | LTL | NMFC | NMFC Sub Item | UFC | Freight Description | Rail Variance |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
No Variation. NMFC and UFCC Match.
MRC | Decoded Requirement | Clear Text Reply |
---|---|---|
CPRW | Actuator Function | TRIP-RESET |
CPRX | Actuator Position Designation | AT EACH POLE |
APNQ | Arc Quenching Method | AIR |
ADAQ | Body Length | 2.500 INCHES NOMINAL |
AAQL | Body Style | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
ADAT | Body Width | 2.250 INCHES NOMINAL |
AJEC | Boss Height | 0.140 INCHES NOMINAL |
ADTV | Case Material | PLASTIC |
AEBP | Center To Center Distance Between Terminals Parallel To Length | 1.938 INCHES NOMINAL |
AEBQ | Center To Center Distance Between Terminals Parallel To Width | 0.750 INCHES NOMINAL |
CPRH | Circuit Protection Type | OVERCURRENT ALL LOCATIONS |
AEBY | Distance Between Centerlines Of Mounting Facilities Parallel To Body Length | 2.062 INCHES NOMINAL |
AEHA | Distance Between Centerlines Of Mounting Facilities Parallel To Body Width | 0.750 INCHES NOMINAL |
CPRY | External Actuator Linkage Arrangement | ONE, TWO, AND THREE LINKED |
AFJN | Fragility Factor | MODERATELY RUGGED |
FREQ | Frequency In Hertz | 60.0 ALL LOCATIONS |
CPLM | Maximum Continuous Load Current Rating Per Pole | 20.0 AMPERES AC ALL LOCATIONS |
CPRG | Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps | 1000.0 AC ALL LOCATIONS |
AXHR | Mounting Facility Type And Quantity | 6 THREADED HOLE |
AJWX | Mounting Surface To Terminal End Distance | 2.611 INCHES NOMINAL |
CQJX | Nominal Thread Size | 0.138 INCHES |
CPRF | Operating Voltage Type And Rating Per Pole In Volts | 250.0 AC ALL LOCATIONS |
CQXF | Inclosure Protection Type For Which Designed | DUSTPROOF |
CPSM | Internal Trip Release Configuration | SERIES TRIP ALL LOCATIONS |
CPRR | Main Contact Tripping Mechanism Type | TRIP FREE |
CPRT | Manual Actuator Type And Quantity | 3 TOGGLE |
AKPX | Pole Quantity | 3 |
CPRQ | Reset Method | MANUAL |
CQWN | Trip Delay Time In Seconds Per Rated Continuous Current | 4.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 10.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CPRL | Trip Release Characteristic | TIME DELAY ALL LOCATIONS |
CPRJ | Trip Release Method | MAGNETIC-HYDRAULIC ALL LOCATIONS |
CPRN | Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent | 150.0 ALL LOCATIONS |
BBRG | Storage Type | GENERAL PURPOSE WAREHOUSE |
TTQY | Terminal Type And Quantity | 6 THREADED STUD |
CMLP | Thread Quantity Per Inch | 32 |
THSD | Thread Series Designator | UNC |