Manufacturer Part Number | RNCC | RNVC | Manufacturer Name | CAGE | |
---|---|---|---|---|---|
ETN4985 | 3 - Design Control Reference | 2 - Production Item | SPD ELECTRICAL SYSTEMS, INC | 30086 |
Design Control Reference. The primary number used to identify an item of production or a range of items of production, by the manufacturer (individual, company, firm, corporation, or Government activity) which controls the design, characteristics, and production of the item by means of its engineering drawings, specifications and inspection requirements.
A design control or other reference number that is an item-identifying number for an item of production, or a source control reference or a specification or standard part, type, or similar reference number that is an item-identifying number for an item of supply.
FSG | FSC | NIIN | FIIG | INC | CRITICALITY | TYPE OF ITEM | MRC | DEMIL | HMIC | EDC | PMIC | ADPEC | DATE CREATED |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
59 | 5925 | 002481111 | A030A0 | 04558 | X | M | 9 | A | P | U | 1 Jan 1963 |
The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.
Partial Descriptive - Reference Item Identification (Type 1A Concept)
A Defense Logistics Information Service-generated code for items lacking but requiring an RPDMRC (i.e., through mass FIIG revision change an item may be downgraded from a type 1 to a reference or partial descriptive method item identification).
Non-MLI/ Non-SLI — Demilitarization not required.
Indicates there is no information in the HMIRS; however, the NSN is in a FSC in Table II of Federal Standard 313 and a MSDS may be required by the user. The requirement for a MSDS is dependent on a hazard determination of the supplier or the intended end use of the product.
Precious Metal Content is unknown.
MOE Rule | Former MOE | AMC | AMSC | NIMSC | IMC | IMC Activity | AAC | DSOR | Collaborators | Receivers | Effective Date | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
ZC01 | 1 Apr 1991 |
ISC | Originator | NIIN Status | Replaced / Replacement ISC | Replaced / Replacement Originator | Replacement NIIN Status | Replacement Date | Replaced / Replacement NSN | Decision Date |
---|---|---|---|---|---|---|---|---|
6 | TX | 0 | 24 Apr 1968 |
An item authorized for procurement that is in a specific Federal Supply Class (FSC) or item name grouping consisting primarily of items which are one-of-a-kind; therefore, little or no potential exists for elimination of items through formal item reduction studies.
Defense Supply Center Columbus, Columbus, OH 43218
Item is active. File data coded KFD is forwarded. if this KFD data represents your item of supply, submit, if applicable, an LAD, LAU, or LCU transaction. Otherwise, use the National Stock Number (NSN) in your supply system.
Integrity | Originating | HMC | LCL | WCC | TCC | SHC | ADC | ACC | ASH | LTL | NMFC | NMFC Sub Item | UFC | Freight Description | Rail Variance |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
P | 658 | Z | 9 | A | H | Z | P | 061300 | X | 34410 | CIRCUIT-BREAKER-SWITCH-NOI |
77.5
Electical Appliances, Small
No special type of cargo code applicable
No special handling required
Shipment is not a consolidation and does not exceed 72 inches in any dimension.
Signal Corps supplies and equipment, including radio equipment and supplies, communications equipment and supplies, electrical equipment and supplies, etc.
No special handling required.
No Variation. NMFC and UFCC Match.
MRC | Decoded Requirement | Clear Text Reply |
---|---|---|
CPRH | Circuit Protection Type | OVERCURRENT ALL LOCATIONS |
CPLM | Maximum Continuous Load Current Rating Per Pole | 100.0 AMPERES DC ALL LOCATIONS |
CPRF | Operating Voltage Type And Rating Per Pole In Volts | 250.0 DC ALL LOCATIONS |
AKPX | Pole Quantity | 2 |
ABKW | Overall Height | 3.531 INCHES NOMINAL |
ABHP | Overall Length | 4.594 INCHES NOMINAL |
ABMK | Overall Width | 3.844 INCHES NOMINAL |
CQWN | Trip Delay Time In Seconds Per Rated Continuous Current | 7.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 25.000 MAXIMUM AT 200 PCT ALL LOCATIONS AND 2.000 MINIMUM AT 300 PCT ALL LOCATIONS AND 4.000 MAXIMUM AT 300 PCT ALL LOCATIONS |
CRCF | Trip Release Ambient Temp Rating | 50.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
CPRL | Trip Release Characteristic | INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
CPRJ | Trip Release Method | MAGNETIC ALL LOCATIONS |
CPRN | Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent | 175.0 ALL LOCATIONS |
TTQY | Terminal Type And Quantity | 4 COMPRESSION |