5925-00-279-1350

CIRCUIT BREAKER


5925-00-279-1350 (5925002791350, 002791350)
Part Numbers (3 listings): 5300065-003 | 1163SMG6-5-125-60-3 | 1163SM6-5A125VCURVE3 |
Summary

FSG 59 / FSC 5925

DEMIL: A

DEMIL INT:

HMIC: P

Date Created: 1 Jan 1963

Unit Weight: None

Unit Size: None

Unit Pack Cube: None

Replacement NSN:

5925-00-283-6517

Replacement Date: 3 Sep 1970

MSDS: None

Hazmat: None

Request a Quote


;



MASTER CROSS REFERENCE LIST (MCRL) | NSN 5925-00-279-1350 Submit RFQ
Manufacturer Part NumberRNCCRNVCManufacturer NameCAGE
5300065-0033 - Design Control Reference9 - No Longer UsedC SYSTEMS LLC  088A2      
5300065-0033 - Design Control Reference9 - No Longer UsedC SYSTEMS LLC  088A2      
1163SMG6-5-125-60-35 - Replaced / Discontinued9 - No Longer UsedEATON CORP  74193    CAGE 74193  
1163SM6-5A125VCURVE35 - Replaced / Discontinued9 - No Longer UsedEATON CORP  74193    CAGE 74193  
1163SM6-5A125VCURVE35 - Replaced / Discontinued9 - No Longer UsedEATON CORP  74193    CAGE 74193  
1163SMG6-5-125-60-35 - Replaced / Discontinued9 - No Longer UsedEATON CORP  74193    CAGE 74193  
Code Definitions

3 - Design Control Reference

Reference Number Category Code (DRN_2910)


Design Control Reference. The primary number used to identify an item of production or a range of items of production, by the manufacturer (individual, company, firm, corporation, or Government activity) which controls the design, characteristics, and production of the item by means of its engineering drawings, specifications and inspection requirements.

5 - Replaced / Discontinued

Reference Number Category Code (DRN_2910)


Secondary Reference. Any additional number, other than a primary number (codes 1,2,3,4) informative reference (code 6) or vendor item drawing reference (code 7) assigned to an item of production or supply by a commercial or Government organization, which represents the same item of production or supply to which the National Stock Number (NSN) was assigned. The reference number may have had an RNCC of 1, 2, 3, 4 or 7 but has since been replaced in the item-of-supply concept of the NSN by another primary number.

9 - No Longer Used

Reference Number Variation Code (DRN_4780)


A specification, standard, or other reference number which is superseded, canceled, obsolete or discontinued and is coded Reference Number Category Code (RNCC) 5; a reference number for information only coded RNCC 6; or a reference number coded RNCC D.


FLIS - SEG A - IDENTIFICATION | NSN 5925-00-279-1350 Submit RFQ
FSGFSCNIINFIIGINCCRITICALITYTYPE OF ITEMMRCDEMILHMICEDCPMICADPECDATE CREATED
595925002791350A030A000136X1APA1 Jan 1963
Code Definitions

59

Federal Supply Group (FSG_3994/FSC_WI_FSG_3996)


Electrical and Electronic Equipment Components

5925

Federal Supply Class (FSC_3994/FSC_WI_FSC_3996)


Circuit Breakers

002791350

National Item Identification Number (NCB_CD_4130/I_I_NBR_4131)


NSN 5925-00-279-1350

A030A0

Federal Item Identification Guide (FIIG_4065)

00136

Item Naming Code (INC_4080)

1 Jan 1963

NIIN Assignment Date (DT_NIIN_ASGMT_2180)

X

Item Criticality (CRITL_CD_FIIG_3843)


The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.

1

Type of Item Identification (TYP_II_4820)


Full Descriptive Item Identification

A

Demilitarization Code (DEMIL_CD_0167)


Non-MLI/ Non-SLI — Demilitarization not required.

P

Hazardous Material Indicator Code (HMIC_0865)


Indicates there is no information in the HMIRS; however, the NSN is in a FSC in Table II of Federal Standard 313 and a MSDS may be required by the user. The requirement for a MSDS is dependent on a hazard determination of the supplier or the intended end use of the product.

A

Precious Metals Indicator Code (PMIC_0802)


Item does not contain Precious Metal.


FLIS - SEG C - REFERENCE NUMBER | NSN 5925-00-279-1350 Submit RFQ
RNFCRNCCRNVCDACRNAACRNSCRNJCSADCMSDSHCCReference NumberCAGE
395TXD5300065-003  088A2  
3596TXB1163SM6-5A125VCURVE3  74193   CAGE/74193
59ETXB1163SMG6-5-125-60-3  74193   CAGE/74193
Code Definitions

3

Reference Number Category Code (RNCC_2910)


Design Control Reference. The primary number used to identify an item of production or a range of items of production, by the manufacturer (individual, company, firm, corporation, or Government activity) which controls the design, characteristics, and production of the item by means of its engineering drawings, specifications and inspection requirements.

9

Reference Number Variation Code (RNVC_4780)


A specification, standard, or other reference number which is superseded, canceled, obsolete or discontinued and is coded Reference Number Category Code (RNCC) 5; a reference number for information only coded RNCC 6; or a reference number coded RNCC D.

5

Document Availability Code (DAC_2640)


The reference number is represented by a drawing, but the drawing was not available to the RNAAC, who may or may not be the submitting activity, at the time of submission of the reference number.

TX

Reference Number Action Activity Code (RNAAC_2900)


Defense Supply Center Columbus, Columbus, OH 43218

D

Reference Number Status Code (RNSC_2923)


Procurement authority of the manufacturer and reference number have not yet been checked. NOTE: This code is to be allocated to reference numbers still requiring checks on procurement authority.

3

Reference Number Format Code (RNFC_2920)


Number format is unknown. (Coded RNFC 3 by the Defense Logistics Information Service upon implementation of FLIS.)

5

Reference Number Category Code (RNCC_2910)


Secondary Reference. Any additional number, other than a primary number (codes 1,2,3,4) informative reference (code 6) or vendor item drawing reference (code 7) assigned to an item of production or supply by a commercial or Government organization, which represents the same item of production or supply to which the National Stock Number (NSN) was assigned. The reference number may have had an RNCC of 1, 2, 3, 4 or 7 but has since been replaced in the item-of-supply concept of the NSN by another primary number.

6

Document Availability Code (DAC_2640)


The reference number is represented by technical documentation other than a drawing but the documentation was not available to the RNAAC, who may or may not be the submitting activity, at the time of submission of the reference number.

B

Reference Number Status Code (RNSC_2923)


Manufacturer and/or reference number are not authorized for procurement. NOTE: This code may be used for obsolete or informative reference numbers only.

E

Document Availability Code (DAC_2640)


The reference number is represented by engineering data other than an engineering drawing. The data is available for unlimited use and will be furnished by the activity identified by the RNAAC upon request.


FLIS - SEG E - ITEM STANDARDIZATION DATA | NSN 5925-00-279-1350 Submit RFQ
ISCOriginatorNIIN StatusReplaced / Replacement ISCReplaced / Replacement OriginatorReplacement NIIN StatusReplacement DateReplaced / Replacement NSNDecision Date
1TX63TX13 Sep 1970 5925002836517 20 Dec 1969
Code Definitions

1

Item Standardization Code (ISC_2650)


An item authorized for procurement as a result of a formal item reduction study and accepted as a replacement for one or more items not authorized for procurement. In addition, in generic relationships, a code 1 item is related to a code 2 item.

TX

Originator of Standardization Decision (ORG_STDZN_DEC_9325)


Defense Supply Center Columbus, Columbus, OH 43218

6

NIIN Status Code (NIIN_STAT_CD_2670)


Item is inactive (no recorded Primary/Secondary Inventory Control Activity (PICA/SICA)). File data coded KFD is forwarded.

3

Replaced / Replacement Item Standardization Code (ISC_2650)


An item which, as a result of a formal item reduction study, is accepted as not authorized for procurement.

1

Replaced / Replacement NIIN Status Code (NIIN_STAT_CD_2670)


Represents an item for which a U.S. activity proposed cancelled-invalid or cancelled-use action or that the NIIN Status Code be changed to 9, and one or more NATO/FC did not concur in the proposal. See volume 4, chapter 4.9.Item is restricted to North Atlantic Treaty Organization/foreign country (NATO/FC) use only.Represents an item for which a U.S. activity proposed cancelled-invalid or cancelled-use action or that the NIIN Status Code be changed to 9, and one or more NATO/FC did not concur in the proposal. Item is restricted to North Atlantic Treaty Organization/foreign country (NATO/FC) use only.

3 Sep 1970

Date of Replacement Standardization Decision (DT_STDZN_DEC_2300)

5925-00-283-6517

Replaced / Replacement NSN (RP_NSN_STD_RL_8977 / RPLM_NSN_STDZ_9525)

20 Dec 1969

Standardization Decision Date (DT_STDZN_DEC_2300)


FLIS - SEG G - FREIGHT DATA | NSN 5925-00-279-1350 Submit RFQ
IntegrityOriginatingHMCLCLWCCTCCSHCADCACCASHLTLNMFCNMFC Sub ItemUFCFreight DescriptionRail Variance
658Z9AHZP061300X34410CIRCUIT-BREAKER-SWITCH-NOI
Code Definitions

XX

Originating Activity Code (ORIG_ACTY_CD_4210)


658

Water Commodity Code (WRT_CMDTY_CD_9275)


Electical Appliances, Small

Z

Type Cargo Code (TYPE_CGO_CD_9260)


No special type of cargo code applicable

9

Special Handling Code (SP_HDLG_CD_9240)


No special handling required

A

Air Dimension Code (AIR_DIM_CD_9220)


Shipment is not a consolidation and does not exceed 72 inches in any dimension.

H

Air Commodity Code (AIR_CMTY_HDLG_9215)


Signal Corps supplies and equipment, including radio equipment and supplies, communications equipment and supplies, electrical equipment and supplies, etc.

Z

Air Special Handling Code (AIR_CMTY_HDLG_9215)


No special handling required.

P

Less Than Truckload (CLAS_RTNG_CD_2770)


77.5

061300

National Motor Freight Classification Number (NMFC Item Number) (NMFC_2850)

X

NMFC Sub Item Number (SUB_ITM_NBR_0861)

34410

Uniform Freight Classification (UFC_CD_MODF_3040)

CIRCUIT-BREAKER-SWITCH-NOI

Freight Description (FRT_DESC_4020)

Rail Variance

Rail Variance (RAIL_VARI_CD_4760)


No Variation. NMFC and UFCC Match.


FLIS - SEG H - MANAGEMENT DATA | NSN 5925-00-279-1350 Submit RFQ
Unit PriceMOESOSAACCIICQUPReparabilityUISLC
DSSMSYU1EA0
Code Definitions

SMS

Source of Supply (SOS_CD_3690) or Source of Supply Modifier (SOSM_CD_2948)


Defense Logistics Agency, Enterprise Business Systems

Y

Acquisition Advice Code (AAC_2507)


TERMINAL ITEM (NON-STOCKED ITEMS) Future procurement is not authorized. No wholesale stock is available for issue. 1. Requisitions will not be processed to the wholesale manager. 2. Internal Service/agency requisitioning may be continued in accordance with the Service/agency requisitioning policies.

U

Controlled Item Inventory Code (CIIC_2863)


Unclassified

1

Quantity Unit Pack (QUP_6106)


1

EA

Unit of Issue (UI_3050)


Each - A numeric quantity of one item of supply. Do not use if a more specific term applies, such as kit, set, assortment, assembly, group, sheet, plate, strip or length.

0

Shelf Life Code (SLC_2943)


TYPE I or TYPE II (Non-Deteriorative/No Shelf-Life) - An individual item of supply which is determined through an evaluation of technical test data and/or actual experience to be an item with a definite non-extendible period of shelf-life OR An individual item of supply having an assigned shelf-life time period that may be extended after completion of inspection/test/restorative action.

DS

Service / Agency Code (MOE_CD_2833)


Defense Logistics Agency


FLIS - SEG W - PACKAGING DATA | NSN 5925-00-279-1350 Submit RFQ
SourcePICA / SICAPackaging CategoryStoragePreservationClean/DryINT QtyUnit WeightUnit SizeUnit Pack CubeItem WeightItem Dims
PP411AAA
Preservation MaterialWrapping MaterialCushioning / DunnageCushioning ThicknessUnit ContainerIntermediate ContainerUnit Container LevelSpecial MarkingLevel A PackingLevel B PackingMinimal PackingOptional Procedure
0000NAXECDO00QQO
Code Definitions

P

Packaging Data Source Code (PK_DTA_SRC_CD_5148)


Primary Inventory Control Activity (PICA)

P

Primary / Secondary Inventory Control Code (PICA_SICA_IND_5099)


Primary Inventory Control Activity (PICA)

41

Method of Preservation Code (MTHD_PRSRV_CD_5160)


Watervaporproof bag, sealed

1

Cleaning and Drying Procedure Code (CLNG_DRY_PRC_5161)


Any suitable process that is not injurious to the item.

AAA

Intermediate Container Quantity (INTMD_CTN_QTY_5152)

Unit Pack Weight (UP_WT_5153)

Unit Pack Cube (UP_CU_5155)

00

Preservation Material Code (PRSRV_MAT_CD_5162)


No requirement

00

Wrapping Material Code (WRAP_MAT_CD_5163)


No requirement

NA

Cushioning and Dunnage Material Code (CUSH_DUN_MAT_5164)


PPP-C-795, cellular plastic film cushioning; or A-A-3129, open cell plastic cushioning; or PPP-C-1797, polypropylene foam cushioning; or A-A-59136, polyethylene foam cushioning

X

Thickness of Cushioning or Dunnage Code (THK_CUSH_DUN_5165)


As required to protect the item or elements of the package

EC

Unit Container Code (UNIT_CTNR_CD_5166)


ASTM-D5118, Type CF, Class domestic, corrugated fiberboard box.

DO

Intermediate Container Code (INTMD_CTNR_CD_5167)


Any suitable fiber box included in this table may be used (see J.4.9.1).

00

Special Marking Code (SP_MKG_CD_5169)


No special marking

Q

Packing Requirement Code - For Level A (Maximum) Packing (LVL_A_PKG_CD_5170)


Packing shall be accomplished in accordance with table C.II for the packing level specified. Closure sealing and reinforcement shall be in accordance with applicable specification for shipping container.

Q

Packing Requirement Code - For Level B (Intermediate) Packing (LVL_B_PKG_CD_5171)


Packing shall be accomplished in accordance with table C-II for the packing level specified. Closure sealing and reinforcement shall be in accordance with the appropriate shipping container specification.

O

Optional Procedure Indicator Code (OPTNL_PRO_IND_5173)


Options can be exercised as to specific method of preservation or DoD approved packaging materials to be used. However, basic preservation method shall be retained, supplemental data shall be complied with, and unit package dimensions shall not be increased by more than one inch. Equal or better protection shall be given the item and there shall be no increase in the package cost.


FLIS - SEG M/V - CHARACTERISTICS DATA | NSN 5925-00-279-1350 Submit RFQ
MRCDecoded RequirementClear Text Reply
CPRWActuator FunctionTRIP-RESET
CPRXActuator Position DesignationAT POLE ONE
APNQArc Quenching MethodMAGNETIC BLOWOUT
ADAUBody Height2.678 INCHES MINIMUM AND 2.698 INCHES MAXIMUM
ADAQBody Length5.240 INCHES MINIMUM AND 5.260 INCHES MAXIMUM
AAQLBody StyleSINGLE POLE TYPE
ADATBody Width1.490 INCHES MINIMUM AND 1.510 INCHES MAXIMUM
AJECBoss Height0.208 INCHES MINIMUM AND 0.228 INCHES MAXIMUM
ADTVCase MaterialPLASTIC
AEBPCenter To Center Distance Between Terminals Parallel To Length4.349 INCHES MINIMUM AND 4.369 INCHES MAXIMUM
CPRHCircuit Protection TypeOVERCURRENT SINGLE LOCATION
AEBYDistance Between Centerlines Of Mounting Facilities Parallel To Body Length4.349 INCHES MINIMUM AND 4.369 INCHES MAXIMUM
AEHADistance Between Centerlines Of Mounting Facilities Parallel To Body Width0.974 INCHES MINIMUM AND 0.994 INCHES MAXIMUM
AFJNFragility FactorMODERATELY RUGGED
FREQFrequency In Hertz60.0 SINGLE LOCATION
CPLMMaximum Continuous Load Current Rating Per Pole5.0 AMPERES AC SINGLE LOCATION
CPRGMaximum Interrupting Capacity Current Type And Rating Per Pole In Amps5000.0 AC SINGLE LOCATION
AXHRMounting Facility Type And Quantity4 THREADED HOLE AND 4 UNTHREADED HOLE
CQJXNominal Thread Size0.164 INCHES
CPRFOperating Voltage Type And Rating Per Pole In Volts125.0 AC SINGLE LOCATION
CQXFInclosure Protection Type For Which DesignedDUSTPROOF AND FUNGUS PROOF
CPSMInternal Trip Release ConfigurationSERIES TRIP SINGLE LOCATION
CPRRMain Contact Tripping Mechanism TypeTRIP FREE
CPRTManual Actuator Type And Quantity1 TOGGLE
AKPXPole Quantity1
CPRQReset MethodMANUAL
CQWNTrip Delay Time In Seconds Per Rated Continuous Current0.350 MINIMUM AT 200 PCT SINGLE LOCATION AND 1.000 MAXIMUM AT 200 PCT SINGLE LOCATION
CPRLTrip Release CharacteristicTIME DELAY SINGLE LOCATION
CPRJTrip Release MethodMAGNETIC-HYDRAULIC SINGLE LOCATION
CPRNUltimate Trip Rating Of Continuous Current Rating Per Pole In Percent125.0 SINGLE LOCATION
AEBVUnthreaded Mounting Hole Diameter0.190 INCHES NOMINAL
BBRGStorage TypeGENERAL PURPOSE WAREHOUSE
TTQYTerminal Type And Quantity2 COMPRESSION
CMLPThread Quantity Per Inch32
THSDThread Series DesignatorUNC


Back to Top
Back to Top