5925-00-518-7763

CIRCUIT BREAKER


5925-00-518-7763 (5925005187763, 005187763)
Part Number (1 listing): TF126070
Summary

FSG 59 / FSC 5925

DEMIL: A

DEMIL INT:

HMIC: P

Date Created: 1 Jan 1963

Request a Quote


;



MASTER CROSS REFERENCE LIST (MCRL) | NSN 5925-00-518-7763 Submit RFQ
Manufacturer Part NumberRNCCRNVCManufacturer NameCAGE
TF1260703 - Design Control Reference2 - Production ItemGENERAL ELECTRIC CO  24446    CAGE 24446  
Code Definitions

3 - Design Control Reference

Reference Number Category Code (DRN_2910)


Design Control Reference. The primary number used to identify an item of production or a range of items of production, by the manufacturer (individual, company, firm, corporation, or Government activity) which controls the design, characteristics, and production of the item by means of its engineering drawings, specifications and inspection requirements.

2 - Production Item

Reference Number Variation Code (DRN_4780)


A design control or other reference number that is an item-identifying number for an item of production, or a source control reference or a specification or standard part, type, or similar reference number that is an item-identifying number for an item of supply.


FLIS - SEG A - IDENTIFICATION | NSN 5925-00-518-7763 Submit RFQ
FSGFSCNIINFIIGINCCRITICALITYTYPE OF ITEMMRCDEMILHMICEDCPMICADPECDATE CREATED
595925005187763A030A000136X49APU1 Jan 1963
Code Definitions

59

Federal Supply Group (FSG_3994/FSC_WI_FSG_3996)


Electrical and Electronic Equipment Components

5925

Federal Supply Class (FSC_3994/FSC_WI_FSC_3996)


Circuit Breakers

005187763

National Item Identification Number (NCB_CD_4130/I_I_NBR_4131)


NSN 5925-00-518-7763

A030A0

Federal Item Identification Guide (FIIG_4065)

00136

Item Naming Code (INC_4080)

1 Jan 1963

NIIN Assignment Date (DT_NIIN_ASGMT_2180)

X

Item Criticality (CRITL_CD_FIIG_3843)


The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.

4

Type of Item Identification (TYP_II_4820)


Partial Descriptive Item Identification (Type 1 Concept)

9

Reference / Partial Descriptive Method Reason Code (RPDMRC_4765)


A Defense Logistics Information Service-generated code for items lacking but requiring an RPDMRC (i.e., through mass FIIG revision change an item may be downgraded from a type 1 to a reference or partial descriptive method item identification).

A

Demilitarization Code (DEMIL_CD_0167)


Non-MLI/ Non-SLI — Demilitarization not required.

P

Hazardous Material Indicator Code (HMIC_0865)


Indicates there is no information in the HMIRS; however, the NSN is in a FSC in Table II of Federal Standard 313 and a MSDS may be required by the user. The requirement for a MSDS is dependent on a hazard determination of the supplier or the intended end use of the product.

U

Precious Metals Indicator Code (PMIC_0802)


Precious Metal Content is unknown.


FLIS - SEG B - MOE RULE DATA | NSN 5925-00-518-7763 Submit RFQ
MOE RuleFormer MOEAMCAMSCNIMSCIMCIMC ActivityAACDSORCollaboratorsReceiversEffective Date
G90000L1 Apr 1991
Code Definitions

0

Acquisition Method Code (AMC_2871)


Not Established

L

Acquisition Advice Code (AAC_2507)


LOCAL PURCHASE (NON-STOCKED ITEMS) Defense Logistics Agency (DLA)/GSA/Service/Agency-managed items authorized for local purchase as normal means of support at base, post, camp or station level. Item not stocked in wholesale distribution system of IMM/Service/Agency ICP.


FLIS - SEG E - ITEM STANDARDIZATION DATA | NSN 5925-00-518-7763 Submit RFQ
ISCOriginatorNIIN StatusReplaced / Replacement ISCReplaced / Replacement OriginatorReplacement NIIN StatusReplacement DateReplaced / Replacement NSNDecision Date
2TX010 May 1971
Code Definitions

2

Item Standardization Code (ISC_2650)


An item authorized for procurement which has been included in an item reduction study and which initially does not replace an item not authorized for procurement. In addition, in generic relationships, a code 2 item is related to a code 1 item.

TX

Originator of Standardization Decision (ORG_STDZN_DEC_9325)


Defense Supply Center Columbus, Columbus, OH 43218

0

NIIN Status Code (NIIN_STAT_CD_2670)


Item is active. File data coded KFD is forwarded. if this KFD data represents your item of supply, submit, if applicable, an LAD, LAU, or LCU transaction. Otherwise, use the National Stock Number (NSN) in your supply system.

10 May 1971

Standardization Decision Date (DT_STDZN_DEC_2300)


FLIS - SEG G - FREIGHT DATA | NSN 5925-00-518-7763 Submit RFQ
IntegrityOriginatingHMCLCLWCCTCCSHCADCACCASHLTLNMFCNMFC Sub ItemUFCFreight DescriptionRail Variance
Code Definitions

XX

Originating Activity Code (ORIG_ACTY_CD_4210)


Rail Variance

Rail Variance (RAIL_VARI_CD_4760)


No Variation. NMFC and UFCC Match.


FLIS - SEG M/V - CHARACTERISTICS DATA | NSN 5925-00-518-7763 Submit RFQ
MRCDecoded RequirementClear Text Reply
CPRWActuator FunctionTRIP W/SEPARATE RESET
APNQArc Quenching MethodDEION
ADTVCase MaterialPLASTIC
CPRHCircuit Protection TypeOVERCURRENT ALL LOCATIONS
FREQFrequency In Hertz60.0 ALL LOCATIONS
CPLMMaximum Continuous Load Current Rating Per Pole70.0 AMPERES AC ALL LOCATIONS AND 70.0 AMPERES DC ALL LOCATIONS
CPRGMaximum Interrupting Capacity Current Type And Rating Per Pole In Amps15000.0 AC ALL LOCATIONS AND 15000.0 DC ALL LOCATIONS
AXHRMounting Facility Type And Quantity2 UNTHREADED HOLE
CPRFOperating Voltage Type And Rating Per Pole In Volts600.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS
CPRRMain Contact Tripping Mechanism TypeTRIP FREE
CPRTManual Actuator Type And Quantity1 TOGGLE
AKPXPole Quantity2
CPRQReset MethodMANUAL
ABKWOverall Height4.812 INCHES NOMINAL
ABHPOverall Length9.375 INCHES NOMINAL
ABMKOverall Width2.750 INCHES NOMINAL
FEATSpecial FeaturesMTG HOLES SPACED 7.250 IN. C TO C
CQWNTrip Delay Time In Seconds Per Rated Continuous Current400.000 MINIMUM AT 125 PCT ALL LOCATIONS AND 6000.000 MAXIMUM AT 125 PCT ALL LOCATIONS AND 52.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 135.000 MAXIMUM AT 200 PCT ALL LOCATIONS AND 21.000 MINIMUM AT 300 PCT ALL LOCATIONS AND 42.000 MAXIMUM AT 300 PCT ALL LOCATIONS
CRCFTrip Release Ambient Temp Rating25.0 DEG CELSIUS NOMINAL ALL LOCATIONS
CPRLTrip Release CharacteristicINSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS
CQQCTrip Release Duty CycleCONTINUOUS ALL LOCATIONS
CPRJTrip Release MethodTHERMAL-MAGNETIC ALL LOCATIONS
CPRNUltimate Trip Rating Of Continuous Current Rating Per Pole In Percent122.0 ALL LOCATIONS
AEBVUnthreaded Mounting Hole Diameter0.281 INCHES NOMINAL
TTQYTerminal Type And Quantity4 SCREW


Back to Top