Manufacturer Part Number | RNCC | RNVC | Manufacturer Name | CAGE | |
---|---|---|---|---|---|
TE32040 | 3 - Design Control Reference | 2 - Production Item | GENERAL ELECTRIC CO | 60969 | ![]() |
TE32040 | 5 - Replaced / Discontinued | 2 - Production Item | GENERAL ELECTRIC CO | 24446 | ![]() |
9975170-3 | 5 - Replaced / Discontinued | 2 - Production Item | U S ARMY AVIATION AND MISSILE | 18876 | ![]() |
Design Control Reference. The primary number used to identify an item of production or a range of items of production, by the manufacturer (individual, company, firm, corporation, or Government activity) which controls the design, characteristics, and production of the item by means of its engineering drawings, specifications and inspection requirements.
Secondary Reference. Any additional number, other than a primary number (codes 1,2,3,4) informative reference (code 6) or vendor item drawing reference (code 7) assigned to an item of production or supply by a commercial or Government organization, which represents the same item of production or supply to which the National Stock Number (NSN) was assigned. The reference number may have had an RNCC of 1, 2, 3, 4 or 7 but has since been replaced in the item-of-supply concept of the NSN by another primary number.
A design control or other reference number that is an item-identifying number for an item of production, or a source control reference or a specification or standard part, type, or similar reference number that is an item-identifying number for an item of supply.
FSG | FSC | NIIN | FIIG | INC | CRITICALITY | TYPE OF ITEM | MRC | DEMIL | HMIC | EDC | PMIC | ADPEC | DATE CREATED |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
59 | 5925 | 008153317 | A030A0 | 00136 | X | M | 9 | A | P | S | 1 Jan 1962 |
The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.
Partial Descriptive - Reference Item Identification (Type 1A Concept)
A Defense Logistics Information Service-generated code for items lacking but requiring an RPDMRC (i.e., through mass FIIG revision change an item may be downgraded from a type 1 to a reference or partial descriptive method item identification).
Non-MLI/ Non-SLI — Demilitarization not required.
Indicates there is no information in the HMIRS; however, the NSN is in a FSC in Table II of Federal Standard 313 and a MSDS may be required by the user. The requirement for a MSDS is dependent on a hazard determination of the supplier or the intended end use of the product.
Item contains silver.
MOE Rule | Former MOE | AMC | AMSC | NIMSC | IMC | IMC Activity | AAC | DSOR | Collaborators | Receivers | Effective Date | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
G150 | 0 | 0 | L | 1 Apr 1991 | ||||||||||||||||||||||||||
G770 | 0 | 0 | L | 1 Apr 1991 | ||||||||||||||||||||||||||
ZC01 | 1 Apr 1991 |
Not Established
LOCAL PURCHASE (NON-STOCKED ITEMS) Defense Logistics Agency (DLA)/GSA/Service/Agency-managed items authorized for local purchase as normal means of support at base, post, camp or station level. Item not stocked in wholesale distribution system of IMM/Service/Agency ICP.
ISC | Originator | NIIN Status | Replaced / Replacement ISC | Replaced / Replacement Originator | Replacement NIIN Status | Replacement Date | Replaced / Replacement NSN | Decision Date |
---|---|---|---|---|---|---|---|---|
3 | TX | 0 | 1 | TX | 0 | 10 Feb 1980 | 5925011878841 | 17 Jan 1970 |
An item which, as a result of a formal item reduction study, is accepted as not authorized for procurement.
Defense Supply Center Columbus, Columbus, OH 43218
Item is active. File data coded KFD is forwarded. if this KFD data represents your item of supply, submit, if applicable, an LAD, LAU, or LCU transaction. Otherwise, use the National Stock Number (NSN) in your supply system.
An item authorized for procurement as a result of a formal item reduction study and accepted as a replacement for one or more items not authorized for procurement. In addition, in generic relationships, a code 1 item is related to a code 2 item.
Integrity | Originating | HMC | LCL | WCC | TCC | SHC | ADC | ACC | ASH | LTL | NMFC | NMFC Sub Item | UFC | Freight Description | Rail Variance |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
No Variation. NMFC and UFCC Match.
DLA Land and Maritime, Columbus, OH 43218 ** No longer valid for input **
TERMINAL ITEM. Identifies items in stock, but future procurement is not authorized. Requisitions may continue to be submitted until stocks are exhausted. Preferred item National Stock Number is normally provided by application of the phrase: When Exhausted Use (NSN). Requisitions will be submitted in accordance with IMM/Service requisitioning procedures as applicable.
Unclassified
No QUP
Each - A numeric quantity of one item of supply. Do not use if a more specific term applies, such as kit, set, assortment, assembly, group, sheet, plate, strip or length.
TYPE I or TYPE II (Non-Deteriorative/No Shelf-Life) - An individual item of supply which is determined through an evaluation of technical test data and/or actual experience to be an item with a definite non-extendible period of shelf-life OR An individual item of supply having an assigned shelf-life time period that may be extended after completion of inspection/test/restorative action.
Department of the Navy
MRC | Decoded Requirement | Clear Text Reply |
---|---|---|
CPRW | Actuator Function | TRIP-RESET |
APNQ | Arc Quenching Method | AIR |
ADTV | Case Material | PLASTIC |
CPRH | Circuit Protection Type | OVERCURRENT ALL LOCATIONS |
FREQ | Frequency In Hertz | 60.0 ALL LOCATIONS |
CPLM | Maximum Continuous Load Current Rating Per Pole | 40.0 AMPERES AC ALL LOCATIONS |
CPRG | Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps | 7500.0 AC ALL LOCATIONS |
AXHR | Mounting Facility Type And Quantity | 4 THREADED HOLE |
CQJX | Nominal Thread Size | 0.164 INCHES |
CPRF | Operating Voltage Type And Rating Per Pole In Volts | 240.0 AC ALL LOCATIONS |
CQXF | Inclosure Protection Type For Which Designed | FUNGUS RESISTANT AND MOISTURE RESISTANT |
CPRR | Main Contact Tripping Mechanism Type | TRIP FREE |
CPRT | Manual Actuator Type And Quantity | 1 TOGGLE |
AKPX | Pole Quantity | 3 |
PRMT | Precious Material | SILVER |
CPRQ | Reset Method | MANUAL |
ABKW | Overall Height | 3.969 INCHES NOMINAL |
ABHP | Overall Length | 6.000 INCHES NOMINAL |
ABMK | Overall Width | 4.125 INCHES NOMINAL |
FEAT | Special Features | MTG HOLES SPACED 4.843 IN. BY 2.750 IN. C TOC |
CQWN | Trip Delay Time In Seconds Per Rated Continuous Current | 80.000 NOMINAL AT 150 PCT ALL LOCATIONS AND 28.000 NOMINAL AT 200 PCT ALL LOCATIONS AND 10.000 NOMINAL AT 300 PCT ALL LOCATIONS AND 1.000 NOMINAL AT 800 PCT ALL LOCATIONS |
CRCF | Trip Release Ambient Temp Rating | 25.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
CPRL | Trip Release Characteristic | TIME DELAY ALL LOCATIONS |
CPRJ | Trip Release Method | THERMAL ALL LOCATIONS |
CPRN | Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent | 125.0 ALL LOCATIONS |
TTQY | Terminal Type And Quantity | 6 SCREW |
THSD | Thread Series Designator | UNC |
CMLP | Thread Quantity Per Inch | 32 |