Manufacturer Part Number | RNCC | RNVC | Manufacturer Name | CAGE | |
---|---|---|---|---|---|
EQP9422 | 3 - Design Control Reference | 2 - Production Item | SPD ELECTRICAL SYSTEMS, INC | 30086 | ![]() |
Design Control Reference. The primary number used to identify an item of production or a range of items of production, by the manufacturer (individual, company, firm, corporation, or Government activity) which controls the design, characteristics, and production of the item by means of its engineering drawings, specifications and inspection requirements.
A design control or other reference number that is an item-identifying number for an item of production, or a source control reference or a specification or standard part, type, or similar reference number that is an item-identifying number for an item of supply.
FSG | FSC | NIIN | FIIG | INC | CRITICALITY | TYPE OF ITEM | MRC | DEMIL | HMIC | EDC | PMIC | ADPEC | DATE CREATED |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
59 | 5925 | 008653388 | A030A0 | 00136 | X | 4 | 6 | A | P | U | 1 Jan 1962 |
The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.
Partial Descriptive Item Identification (Type 1 Concept)
An approved item name and FIIG may exist, but it has previously been established and documented that industry refuses to provide the technical data sufficient for preparation on a full descriptive method item identification based on policy, restricted or proprietary data rights, nonexistence of technical data, etc.
Non-MLI/ Non-SLI — Demilitarization not required.
Indicates there is no information in the HMIRS; however, the NSN is in a FSC in Table II of Federal Standard 313 and a MSDS may be required by the user. The requirement for a MSDS is dependent on a hazard determination of the supplier or the intended end use of the product.
Precious Metal Content is unknown.
MOE Rule | Former MOE | AMC | AMSC | NIMSC | IMC | IMC Activity | AAC | DSOR | Collaborators | Receivers | Effective Date | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
ZC01 | 1 Apr 1991 |
RNFC | RNCC | RNVC | DAC | RNAAC | RNSC | RNJC | SADC | MSDS | HCC | Reference Number | CAGE | |
---|---|---|---|---|---|---|---|---|---|---|---|---|
3 | 3 | 2 | 6 | TX | D | EQP9422 | 30086 | ![]() |
Number format is unknown. (Coded RNFC 3 by the Defense Logistics Information Service upon implementation of FLIS.)
Design Control Reference. The primary number used to identify an item of production or a range of items of production, by the manufacturer (individual, company, firm, corporation, or Government activity) which controls the design, characteristics, and production of the item by means of its engineering drawings, specifications and inspection requirements.
A design control or other reference number that is an item-identifying number for an item of production, or a source control reference or a specification or standard part, type, or similar reference number that is an item-identifying number for an item of supply.
The reference number is represented by technical documentation other than a drawing but the documentation was not available to the RNAAC, who may or may not be the submitting activity, at the time of submission of the reference number.
Defense Supply Center Columbus, Columbus, OH 43218
Procurement authority of the manufacturer and reference number have not yet been checked. NOTE: This code is to be allocated to reference numbers still requiring checks on procurement authority.
ISC | Originator | NIIN Status | Replaced / Replacement ISC | Replaced / Replacement Originator | Replacement NIIN Status | Replacement Date | Replaced / Replacement NSN | Decision Date |
---|---|---|---|---|---|---|---|---|
3 | TX | 1 | 1 | TX | 0 | 8 Jul 1970 | 5925009987441 | 17 Oct 1971 |
An item which, as a result of a formal item reduction study, is accepted as not authorized for procurement.
Defense Supply Center Columbus, Columbus, OH 43218
Represents an item for which a U.S. activity proposed cancelled-invalid or cancelled-use action or that the NIIN Status Code be changed to 9, and one or more NATO/FC did not concur in the proposal. See volume 4, chapter 4.9.Item is restricted to North Atlantic Treaty Organization/foreign country (NATO/FC) use only.Represents an item for which a U.S. activity proposed cancelled-invalid or cancelled-use action or that the NIIN Status Code be changed to 9, and one or more NATO/FC did not concur in the proposal. Item is restricted to North Atlantic Treaty Organization/foreign country (NATO/FC) use only.
An item authorized for procurement as a result of a formal item reduction study and accepted as a replacement for one or more items not authorized for procurement. In addition, in generic relationships, a code 1 item is related to a code 2 item.
Item is active. File data coded KFD is forwarded. if this KFD data represents your item of supply, submit, if applicable, an LAD, LAU, or LCU transaction. Otherwise, use the National Stock Number (NSN) in your supply system.
Integrity | Originating | HMC | LCL | WCC | TCC | SHC | ADC | ACC | ASH | LTL | NMFC | NMFC Sub Item | UFC | Freight Description | Rail Variance |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
P | 658 | Z | 9 | A | H | Z | M | 061360 | X | 34430 | COILS-YOKES-FOCUS-DEFLECTION-TV |
77.5
Electical Appliances, Small
No special type of cargo code applicable
No special handling required
Shipment is not a consolidation and does not exceed 72 inches in any dimension.
Signal Corps supplies and equipment, including radio equipment and supplies, communications equipment and supplies, electrical equipment and supplies, etc.
No special handling required.
85
No Variation. NMFC and UFCC Match.
MRC | Decoded Requirement | Clear Text Reply |
---|---|---|
APNQ | Arc Quenching Method | DEION |
ADTV | Case Material | PLASTIC |
CPRH | Circuit Protection Type | OVERCURRENT ALL LOCATIONS |
CPLM | Maximum Continuous Load Current Rating Per Pole | 20.0 AMPERES AC ALL LOCATIONS |
CPRG | Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps | 5000.0 AC ALL LOCATIONS |
AXHR | Mounting Facility Type And Quantity | 2 SLOT |
ABTD | Mounting Slot Width | 0.043 INCHES NOMINAL |
CPRF | Operating Voltage Type And Rating Per Pole In Volts | 240.0 AC ALL LOCATIONS |
CPRR | Main Contact Tripping Mechanism Type | TRIP FREE |
CPRT | Manual Actuator Type And Quantity | 1 TOGGLE |
AKPX | Pole Quantity | 2 |
CPRQ | Reset Method | MANUAL |
ABKW | Overall Height | 2.560 INCHES NOMINAL |
ABHP | Overall Length | 2.000 INCHES NOMINAL |
ABMK | Overall Width | 2.880 INCHES NOMINAL |
CQWN | Trip Delay Time In Seconds Per Rated Continuous Current | 60.000 NOMINAL AT 150 PCT ALL LOCATIONS AND 20.000 NOMINAL AT 200 PCT ALL LOCATIONS AND 6.000 NOMINAL AT 300 PCT ALL LOCATIONS |
CRCF | Trip Release Ambient Temp Rating | 25.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
CPRL | Trip Release Characteristic | TIME DELAY ALL LOCATIONS |
CPRJ | Trip Release Method | THERMAL ALL LOCATIONS |
CPRN | Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent | 125.0 ALL LOCATIONS |
BBRG | Storage Type | GENERAL PURPOSE WAREHOUSE |