Manufacturer Part Number | RNCC | RNVC | Manufacturer Name | CAGE | |
---|---|---|---|---|---|
AM12MG3-7-5-77 | 3 - Design Control Reference | 9 - No Longer Used | EATON CORP | 74193 |
Design Control Reference. The primary number used to identify an item of production or a range of items of production, by the manufacturer (individual, company, firm, corporation, or Government activity) which controls the design, characteristics, and production of the item by means of its engineering drawings, specifications and inspection requirements.
A specification, standard, or other reference number which is superseded, canceled, obsolete or discontinued and is coded Reference Number Category Code (RNCC) 5; a reference number for information only coded RNCC 6; or a reference number coded RNCC D.
FSG | FSC | NIIN | FIIG | INC | CRITICALITY | TYPE OF ITEM | MRC | DEMIL | HMIC | EDC | PMIC | ADPEC | DATE CREATED |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
59 | 5925 | 009181474 | A030A0 | 00136 | X | M | 9 | A | P | U | 1 Jan 1960 |
The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.
Partial Descriptive - Reference Item Identification (Type 1A Concept)
A Defense Logistics Information Service-generated code for items lacking but requiring an RPDMRC (i.e., through mass FIIG revision change an item may be downgraded from a type 1 to a reference or partial descriptive method item identification).
Non-MLI/ Non-SLI — Demilitarization not required.
Indicates there is no information in the HMIRS; however, the NSN is in a FSC in Table II of Federal Standard 313 and a MSDS may be required by the user. The requirement for a MSDS is dependent on a hazard determination of the supplier or the intended end use of the product.
Precious Metal Content is unknown.
MOE Rule | Former MOE | AMC | AMSC | NIMSC | IMC | IMC Activity | AAC | DSOR | Collaborators | Receivers | Effective Date | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
ZR01 | 1 Apr 1991 |
ISC | Originator | NIIN Status | Replaced / Replacement ISC | Replaced / Replacement Originator | Replacement NIIN Status | Replacement Date | Replaced / Replacement NSN | Decision Date |
---|---|---|---|---|---|---|---|---|
3 | TX | 1 | 1 | TX | 0 | 6 May 1969 | 5925000502938 | 28 Apr 1970 |
An item which, as a result of a formal item reduction study, is accepted as not authorized for procurement.
Defense Supply Center Columbus, Columbus, OH 43218
Represents an item for which a U.S. activity proposed cancelled-invalid or cancelled-use action or that the NIIN Status Code be changed to 9, and one or more NATO/FC did not concur in the proposal. See volume 4, chapter 4.9.Item is restricted to North Atlantic Treaty Organization/foreign country (NATO/FC) use only.Represents an item for which a U.S. activity proposed cancelled-invalid or cancelled-use action or that the NIIN Status Code be changed to 9, and one or more NATO/FC did not concur in the proposal. Item is restricted to North Atlantic Treaty Organization/foreign country (NATO/FC) use only.
An item authorized for procurement as a result of a formal item reduction study and accepted as a replacement for one or more items not authorized for procurement. In addition, in generic relationships, a code 1 item is related to a code 2 item.
Item is active. File data coded KFD is forwarded. if this KFD data represents your item of supply, submit, if applicable, an LAD, LAU, or LCU transaction. Otherwise, use the National Stock Number (NSN) in your supply system.
Integrity | Originating | HMC | LCL | WCC | TCC | SHC | ADC | ACC | ASH | LTL | NMFC | NMFC Sub Item | UFC | Freight Description | Rail Variance |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
P | 658 | Z | 9 | A | H | Z | M | 061360 | X | 34430 | COILS-YOKES-FOCUS-DEFLECTION-TV |
77.5
Electical Appliances, Small
No special type of cargo code applicable
No special handling required
Shipment is not a consolidation and does not exceed 72 inches in any dimension.
Signal Corps supplies and equipment, including radio equipment and supplies, communications equipment and supplies, electrical equipment and supplies, etc.
No special handling required.
85
No Variation. NMFC and UFCC Match.
MRC | Decoded Requirement | Clear Text Reply |
---|---|---|
CPRW | Actuator Function | RESET |
APNQ | Arc Quenching Method | MAGNETIC BLOWOUT |
ADTV | Case Material | PLASTIC |
CPRH | Circuit Protection Type | OVERCURRENT SINGLE LOCATION |
AEBY | Distance Between Centerlines Of Mounting Facilities Parallel To Body Length | 2.062 INCHES NOMINAL |
FREQ | Frequency In Hertz | 60.0 SINGLE LOCATION |
CPLM | Maximum Continuous Load Current Rating Per Pole | 7.5 AMPERES AC SINGLE LOCATION |
CPRG | Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps | 1000.0 AC SINGLE LOCATION |
AXHR | Mounting Facility Type And Quantity | 2 THREADED HOLE |
CQJX | Nominal Thread Size | 0.138 INCHES |
CPRF | Operating Voltage Type And Rating Per Pole In Volts | 250.0 AC SINGLE LOCATION |
CQXF | Inclosure Protection Type For Which Designed | EXPLOSION PROOF AND FUNGUS RESISTANT AND MOISTURE RESISTANT |
CPRR | Main Contact Tripping Mechanism Type | TRIP FREE |
CPRT | Manual Actuator Type And Quantity | 1 TOGGLE |
AKPX | Pole Quantity | 1 |
CPRQ | Reset Method | MANUAL |
ABKW | Overall Height | 2.530 INCHES NOMINAL |
ABHP | Overall Length | 3.330 INCHES NOMINAL |
ABMK | Overall Width | 0.760 INCHES NOMINAL |
CPRL | Trip Release Characteristic | INSTANTANEOUS SINGLE LOCATION AND TIME DELAY SINGLE LOCATION |
CQWN | Trip Delay Time In Seconds Per Rated Continuous Current | 0.600 MINIMUM AT 150 PCT SINGLE LOCATION AND 2.000 MAXIMUM AT 150 PCT SINGLE LOCATION AND 0.250 MINIMUM AT 200 PCT SINGLE LOCATION AND 0.800 MAXIMUM AT 200 PCT SINGLE LOCATION AND 0.090 MINIMUM AT 300 PCT SINGLE LOCATION AND 0.190 MAXIMUM AT 300 PCT SINGLE LOCATION |
CPRJ | Trip Release Method | MAGNETIC SINGLE LOCATION |
CPRN | Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent | 125.0 SINGLE LOCATION |
TTQY | Terminal Type And Quantity | 2 THREADED STUD |
THSD | Thread Series Designator | UNC |
CMLP | Thread Quantity Per Inch | 32 |