Manufacturer Part Number | RNCC | RNVC | Manufacturer Name | CAGE | |
---|---|---|---|---|---|
ET1574E1A | 3 - Design Control Reference | 2 - Production Item | SPD ELECTRICAL SYSTEMS, INC | 30086 | ![]() |
Design Control Reference. The primary number used to identify an item of production or a range of items of production, by the manufacturer (individual, company, firm, corporation, or Government activity) which controls the design, characteristics, and production of the item by means of its engineering drawings, specifications and inspection requirements.
A design control or other reference number that is an item-identifying number for an item of production, or a source control reference or a specification or standard part, type, or similar reference number that is an item-identifying number for an item of supply.
FSG | FSC | NIIN | FIIG | INC | CRITICALITY | TYPE OF ITEM | MRC | DEMIL | HMIC | EDC | PMIC | ADPEC | DATE CREATED |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
59 | 5925 | 009658497 | A030A0 | 00136 | X | M | 9 | A | P | U | 1 Jan 1960 |
The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.
Partial Descriptive - Reference Item Identification (Type 1A Concept)
A Defense Logistics Information Service-generated code for items lacking but requiring an RPDMRC (i.e., through mass FIIG revision change an item may be downgraded from a type 1 to a reference or partial descriptive method item identification).
Non-MLI/ Non-SLI — Demilitarization not required.
Indicates there is no information in the HMIRS; however, the NSN is in a FSC in Table II of Federal Standard 313 and a MSDS may be required by the user. The requirement for a MSDS is dependent on a hazard determination of the supplier or the intended end use of the product.
Precious Metal Content is unknown.
MOE Rule | Former MOE | AMC | AMSC | NIMSC | IMC | IMC Activity | AAC | DSOR | Collaborators | Receivers | Effective Date | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
G770 | 0 | 0 | L | 1 Apr 1991 |
Not Established
LOCAL PURCHASE (NON-STOCKED ITEMS) Defense Logistics Agency (DLA)/GSA/Service/Agency-managed items authorized for local purchase as normal means of support at base, post, camp or station level. Item not stocked in wholesale distribution system of IMM/Service/Agency ICP.
ISC | Originator | NIIN Status | Replaced / Replacement ISC | Replaced / Replacement Originator | Replacement NIIN Status | Replacement Date | Replaced / Replacement NSN | Decision Date |
---|---|---|---|---|---|---|---|---|
2 | TX | 0 | 10 May 1971 |
An item authorized for procurement which has been included in an item reduction study and which initially does not replace an item not authorized for procurement. In addition, in generic relationships, a code 2 item is related to a code 1 item.
Defense Supply Center Columbus, Columbus, OH 43218
Item is active. File data coded KFD is forwarded. if this KFD data represents your item of supply, submit, if applicable, an LAD, LAU, or LCU transaction. Otherwise, use the National Stock Number (NSN) in your supply system.
Integrity | Originating | HMC | LCL | WCC | TCC | SHC | ADC | ACC | ASH | LTL | NMFC | NMFC Sub Item | UFC | Freight Description | Rail Variance |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
No Variation. NMFC and UFCC Match.
MRC | Decoded Requirement | Clear Text Reply |
---|---|---|
APNQ | Arc Quenching Method | DEION |
ADTV | Case Material | METAL |
CPRH | Circuit Protection Type | OVERCURRENT ALL LOCATIONS |
CPLM | Maximum Continuous Load Current Rating Per Pole | 40.0 AMPERES AC ALL LOCATIONS |
CPRG | Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps | 7500.0 AC ALL LOCATIONS |
AXHR | Mounting Facility Type And Quantity | 4 UNTHREADED HOLE |
CQJX | Nominal Thread Size | 0.250 INCHES |
CPRF | Operating Voltage Type And Rating Per Pole In Volts | 240.0 AC ALL LOCATIONS |
CQXF | Inclosure Protection Type For Which Designed | DUSTPROOF |
CPRR | Main Contact Tripping Mechanism Type | TRIP FREE |
CPRT | Manual Actuator Type And Quantity | 1 TOGGLE |
AKPX | Pole Quantity | 3 |
CPRQ | Reset Method | MANUAL |
ABKW | Overall Height | 9.625 INCHES NOMINAL |
ABHP | Overall Length | 13.093 INCHES NOMINAL |
ABMK | Overall Width | 6.687 INCHES NOMINAL |
FEAT | Special Features | FLUSH MTD ON 11.750 IN. BY 8.000 IN. MTG CENTERS |
CQWN | Trip Delay Time In Seconds Per Rated Continuous Current | 30.000 MINIMUM AT 150 PCT ALL LOCATIONS AND 240.000 MAXIMUM AT 150 PCT ALL LOCATIONS AND 3.000 MINIMUM AT 500 PCT ALL LOCATIONS AND 5.000 MAXIMUM AT 500 PCT ALL LOCATIONS |
CRCF | Trip Release Ambient Temp Rating | 25.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
CPRL | Trip Release Characteristic | INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
CQQC | Trip Release Duty Cycle | CONTINUOUS ALL LOCATIONS |
CPRJ | Trip Release Method | THERMAL ALL LOCATIONS |
CPRN | Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent | 115.0 ALL LOCATIONS |
TTQY | Terminal Type And Quantity | 6 PIN |