Manufacturer Part Number | RNCC | RNVC | Manufacturer Name | CAGE | |
---|---|---|---|---|---|
TRP1120 | 3 - Design Control Reference | 2 - Production Item | GENERAL ELECTRIC CO | 24446 | ![]() |
Design Control Reference. The primary number used to identify an item of production or a range of items of production, by the manufacturer (individual, company, firm, corporation, or Government activity) which controls the design, characteristics, and production of the item by means of its engineering drawings, specifications and inspection requirements.
A design control or other reference number that is an item-identifying number for an item of production, or a source control reference or a specification or standard part, type, or similar reference number that is an item-identifying number for an item of supply.
FSG | FSC | NIIN | FIIG | INC | CRITICALITY | TYPE OF ITEM | MRC | DEMIL | HMIC | EDC | PMIC | ADPEC | DATE CREATED |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
59 | 5925 | 009750975 | A030A0 | 00136 | X | M | 9 | A | P | U | 1 Jan 1962 |
The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.
Partial Descriptive - Reference Item Identification (Type 1A Concept)
A Defense Logistics Information Service-generated code for items lacking but requiring an RPDMRC (i.e., through mass FIIG revision change an item may be downgraded from a type 1 to a reference or partial descriptive method item identification).
Non-MLI/ Non-SLI — Demilitarization not required.
Indicates there is no information in the HMIRS; however, the NSN is in a FSC in Table II of Federal Standard 313 and a MSDS may be required by the user. The requirement for a MSDS is dependent on a hazard determination of the supplier or the intended end use of the product.
Precious Metal Content is unknown.
MOE Rule | Former MOE | AMC | AMSC | NIMSC | IMC | IMC Activity | AAC | DSOR | Collaborators | Receivers | Effective Date | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
G900 | 0 | 0 | L | 1 Apr 1991 |
Not Established
LOCAL PURCHASE (NON-STOCKED ITEMS) Defense Logistics Agency (DLA)/GSA/Service/Agency-managed items authorized for local purchase as normal means of support at base, post, camp or station level. Item not stocked in wholesale distribution system of IMM/Service/Agency ICP.
ISC | Originator | NIIN Status | Replaced / Replacement ISC | Replaced / Replacement Originator | Replacement NIIN Status | Replacement Date | Replaced / Replacement NSN | Decision Date |
---|---|---|---|---|---|---|---|---|
2 | TX | 0 | 10 May 1971 |
An item authorized for procurement which has been included in an item reduction study and which initially does not replace an item not authorized for procurement. In addition, in generic relationships, a code 2 item is related to a code 1 item.
Defense Supply Center Columbus, Columbus, OH 43218
Item is active. File data coded KFD is forwarded. if this KFD data represents your item of supply, submit, if applicable, an LAD, LAU, or LCU transaction. Otherwise, use the National Stock Number (NSN) in your supply system.
Integrity | Originating | HMC | LCL | WCC | TCC | SHC | ADC | ACC | ASH | LTL | NMFC | NMFC Sub Item | UFC | Freight Description | Rail Variance |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
No Variation. NMFC and UFCC Match.
MRC | Decoded Requirement | Clear Text Reply |
---|---|---|
CPRW | Actuator Function | TRIP-RESET |
CPRX | Actuator Position Designation | AT POLE ONE |
APNQ | Arc Quenching Method | DEION |
ADTV | Case Material | PLASTIC |
CPRH | Circuit Protection Type | OVERCURRENT SINGLE LOCATION |
FREQ | Frequency In Hertz | 60.0 SINGLE LOCATION |
CPLM | Maximum Continuous Load Current Rating Per Pole | 20.0 AMPERES AC SINGLE LOCATION |
CPRG | Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps | 5000.0 AC SINGLE LOCATION |
CPRF | Operating Voltage Type And Rating Per Pole In Volts | 120.0 AC SINGLE LOCATION |
CPRR | Main Contact Tripping Mechanism Type | TRIP FREE |
CPRT | Manual Actuator Type And Quantity | 1 TOGGLE |
AKPX | Pole Quantity | 1 |
CPRQ | Reset Method | MANUAL |
ABKW | Overall Height | 2.921 INCHES NOMINAL |
ABHP | Overall Length | 2.843 INCHES NOMINAL |
ABMK | Overall Width | 0.968 INCHES NOMINAL |
FEAT | Special Features | MOUNTING TYPE IS TERMINAL |
CQWN | Trip Delay Time In Seconds Per Rated Continuous Current | 90.000 MINIMUM AT 150 PCT SINGLE LOCATION AND 200.000 MAXIMUM AT 150 PCT SINGLE LOCATION AND 30.000 MINIMUM AT 200 PCT SINGLE LOCATION AND 55.000 MAXIMUM AT 200 PCT SINGLE LOCATION AND 14.000 MINIMUM AT 300 PCT SINGLE LOCATION AND 26.000 MAXIMUM AT 300 PCT SINGLE LOCATION AND 8.000 MINIMUM AT 400 PCT SINGLE LOCATION AND 14.000 MAXIMUM AT 400 PCT SINGLE LOCATION AND 5.000 MINIMUM AT 500 PCT SINGLE LOCATION AND 9.000 MAXIMUM AT 500 PCT SINGLE LOCATION |
CRCF | Trip Release Ambient Temp Rating | 25.0 DEG CELSIUS NOMINAL SINGLE LOCATION |
CPRL | Trip Release Characteristic | TIME DELAY SINGLE LOCATION |
CQQC | Trip Release Duty Cycle | CONTINUOUS SINGLE LOCATION |
CPRJ | Trip Release Method | THERMAL-MAGNETIC SINGLE LOCATION |
CPRN | Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent | 125.0 SINGLE LOCATION |
TTQY | Terminal Type And Quantity | 1 SCREW AND 1 QUICK DISCONNECT, MALE |