Manufacturer Part Number | RNCC | RNVC | Manufacturer Name | CAGE | |
---|---|---|---|---|---|
8131RTV | 3 - Design Control Reference | 1 - Incomplete Part Number | EATON CORP | 74193 | ![]() |
Design Control Reference. The primary number used to identify an item of production or a range of items of production, by the manufacturer (individual, company, firm, corporation, or Government activity) which controls the design, characteristics, and production of the item by means of its engineering drawings, specifications and inspection requirements.
A design control or other reference number that does NOT identify an item of production without the use of additional information, or a specific part, type, or similar reference number does NOT identify or item of supply without the use of additional information.
FSG | FSC | NIIN | FIIG | INC | CRITICALITY | TYPE OF ITEM | MRC | DEMIL | HMIC | EDC | PMIC | ADPEC | DATE CREATED |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
59 | 5925 | 010199696 | A030A0 | 00136 | X | 1 | A | P | U | 25 Apr 1976 |
The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.
Full Descriptive Item Identification
Non-MLI/ Non-SLI — Demilitarization not required.
Indicates there is no information in the HMIRS; however, the NSN is in a FSC in Table II of Federal Standard 313 and a MSDS may be required by the user. The requirement for a MSDS is dependent on a hazard determination of the supplier or the intended end use of the product.
Precious Metal Content is unknown.
MOE Rule | Former MOE | AMC | AMSC | NIMSC | IMC | IMC Activity | AAC | DSOR | Collaborators | Receivers | Effective Date | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
G860 | 0 | 0 | C | 1 Apr 1991 |
Not Established
SERVICE/AGENCY-MANAGED (Service/Agency use only.) Issue, transfer, or shipment is not subject to specialized controls other than those imposed by individual Services supply policy. 1. The item is centrally managed, stocked, and issued. 2. Requisitions will be submitted in accordance with Service requisitioning procedures.
RNFC | RNCC | RNVC | DAC | RNAAC | RNSC | RNJC | SADC | MSDS | HCC | Reference Number | CAGE | |
---|---|---|---|---|---|---|---|---|---|---|---|---|
1 | 3 | 1 | 4 | 75 | D | 8131RTV | 74193 | ![]() |
Number is formatted as configured on the originating document with the exception of the modification required in volume 2, chapter 2.9.Number is formatted as configured on the originating document with the exception of the modification required in volume 2, chapter 2.9 .
Design Control Reference. The primary number used to identify an item of production or a range of items of production, by the manufacturer (individual, company, firm, corporation, or Government activity) which controls the design, characteristics, and production of the item by means of its engineering drawings, specifications and inspection requirements.
A design control or other reference number that does NOT identify an item of production without the use of additional information, or a specific part, type, or similar reference number does NOT identify or item of supply without the use of additional information.
The reference number is represented by technical documentation other than a drawing and the documentation was available to the RNAAC, who may or may not be the submitting activity, at the time of submission of the reference number; however, the RNAAC cannot furnish the technical documentation.
GSA, FSS/FCSC Washington, DC 20406
Procurement authority of the manufacturer and reference number have not yet been checked. NOTE: This code is to be allocated to reference numbers still requiring checks on procurement authority.
ISC | Originator | NIIN Status | Replaced / Replacement ISC | Replaced / Replacement Originator | Replacement NIIN Status | Replacement Date | Replaced / Replacement NSN | Decision Date |
---|---|---|---|---|---|---|---|---|
5 | 97 | 0 | 25 Apr 1976 |
An item authorized for procurement that has not yet been subject to item standardization.
DLIS-LFF, Battle Creek, MI 49037-3084
Item is active. File data coded KFD is forwarded. if this KFD data represents your item of supply, submit, if applicable, an LAD, LAU, or LCU transaction. Otherwise, use the National Stock Number (NSN) in your supply system.
Integrity | Originating | HMC | LCL | WCC | TCC | SHC | ADC | ACC | ASH | LTL | NMFC | NMFC Sub Item | UFC | Freight Description | Rail Variance |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
86 |
NASA Kennedy Space Center, Kennedy Space Center, FL 32899
No Variation. NMFC and UFCC Match.
MRC | Decoded Requirement | Clear Text Reply |
---|---|---|
CPRW | Actuator Function | TRIP-RESET |
CPRX | Actuator Position Designation | AT POLE ONE |
ADAU | Body Height | 2.640 INCHES NOMINAL |
ADAQ | Body Length | 3.219 INCHES NOMINAL |
AAQL | Body Style | SINGLE POLE TYPE |
ADAT | Body Width | 1.469 INCHES NOMINAL |
AJEC | Boss Height | 0.125 INCHES NOMINAL |
ADTV | Case Material | PLASTIC |
AEBP | Center To Center Distance Between Terminals Parallel To Length | 2.500 INCHES NOMINAL |
CPRH | Circuit Protection Type | OVERCURRENT SINGLE LOCATION |
AEBY | Distance Between Centerlines Of Mounting Facilities Parallel To Body Length | 1.312 INCHES NOMINAL |
FREQ | Frequency In Hertz | 60.0 SINGLE LOCATION |
CPLM | Maximum Continuous Load Current Rating Per Pole | 4.75 AMPERES AC SINGLE LOCATION |
CPRG | Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps | 1500.0 AC SINGLE LOCATION |
AXHR | Mounting Facility Type And Quantity | 2 SLOT |
ABTD | Mounting Slot Width | 0.164 INCHES NOMINAL |
CPRF | Operating Voltage Type And Rating Per Pole In Volts | 250.0 AC SINGLE LOCATION |
CPSM | Internal Trip Release Configuration | RELAY TRIP SINGLE LOCATION |
CPRR | Main Contact Tripping Mechanism Type | TRIP FREE |
CPRT | Manual Actuator Type And Quantity | 1 TOGGLE |
AKPX | Pole Quantity | 1 |
CPRQ | Reset Method | MANUAL |
FEAT | Special Features | SHOCK/VIBRATION RESISTANT 15 G SHOCK,10 G VIBRATION |
CQWN | Trip Delay Time In Seconds Per Rated Continuous Current | 175.000 MINIMUM AT 125 PCT SINGLE LOCATION AND 600.000 MAXIMUM AT 125 PCT SINGLE LOCATION AND 100.000 MINIMUM AT 150 PCT SINGLE LOCATION AND 300.000 MAXIMUM AT 150 PCT SINGLE LOCATION AND 40.000 MINIMUM AT 200 PCT SINGLE LOCATION AND 140.000 MAXIMUM AT 200 PCT SINGLE LOCATION AND 20.000 MINIMUM AT 300 PCT SINGLE LOCATION AND 50.000 MAXIMUM AT 300 PCT SINGLE LOCATION AND 6.500 MINIMUM AT 400 PCT SINGLE LOCATION AND 10.750 MAXIMUM AT 400 PCT SINGLE LOCATION AND 4.000 MINIMUM AT 500 PCT SINGLE LOCATION AND 10.000 MAXIMUM AT 500 PCT SINGLE LOCATION AND 0.030 MINIMUM AT 1000 PCT SINGLE LOCATION AND 0.080 MAXIMUM AT 1000 PCT SINGLE LOCATION |
CPRL | Trip Release Characteristic | TIME DELAY SINGLE LOCATION |
CPRJ | Trip Release Method | MAGNETIC SINGLE LOCATION |
CPRN | Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent | 125.0 SINGLE LOCATION |
CPRP | Ultimate Trip Time Per Pole In Seconds | 105.000 MINIMUM SINGLE LOCATION AND 150.000 MAXIMUM SINGLE LOCATION |
TTQY | Terminal Type And Quantity | 1 THREADED STUD AND 2 SCREW |