Manufacturer Part Number | RNCC | RNVC | Manufacturer Name | CAGE | |
---|---|---|---|---|---|
TEB122100 | 3 - Design Control Reference | 2 - Production Item | GENERAL ELECTRIC CO | 60969 | ![]() |
Design Control Reference. The primary number used to identify an item of production or a range of items of production, by the manufacturer (individual, company, firm, corporation, or Government activity) which controls the design, characteristics, and production of the item by means of its engineering drawings, specifications and inspection requirements.
A design control or other reference number that is an item-identifying number for an item of production, or a source control reference or a specification or standard part, type, or similar reference number that is an item-identifying number for an item of supply.
FSG | FSC | NIIN | FIIG | INC | CRITICALITY | TYPE OF ITEM | MRC | DEMIL | HMIC | EDC | PMIC | ADPEC | DATE CREATED |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
59 | 5925 | 010289336 | A030A0 | 00136 | X | 4 | 3 | A | P | U | 13 Oct 1976 |
The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.
Partial Descriptive Item Identification (Type 1 Concept)
An approved item name and FIIG exist but the item involved is so unique in design that it cannot be fully described in accordance with the FIIG.
Non-MLI/ Non-SLI — Demilitarization not required.
Indicates there is no information in the HMIRS; however, the NSN is in a FSC in Table II of Federal Standard 313 and a MSDS may be required by the user. The requirement for a MSDS is dependent on a hazard determination of the supplier or the intended end use of the product.
Precious Metal Content is unknown.
MOE Rule | Former MOE | AMC | AMSC | NIMSC | IMC | IMC Activity | AAC | DSOR | Collaborators | Receivers | Effective Date | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
G900 | 0 | 0 | L | 1 Apr 1991 |
Not Established
LOCAL PURCHASE (NON-STOCKED ITEMS) Defense Logistics Agency (DLA)/GSA/Service/Agency-managed items authorized for local purchase as normal means of support at base, post, camp or station level. Item not stocked in wholesale distribution system of IMM/Service/Agency ICP.
RNFC | RNCC | RNVC | DAC | RNAAC | RNSC | RNJC | SADC | MSDS | HCC | Reference Number | CAGE | |
---|---|---|---|---|---|---|---|---|---|---|---|---|
3 | 2 | 4 | 75 | TEB122100 | 60969 | ![]() |
Design Control Reference. The primary number used to identify an item of production or a range of items of production, by the manufacturer (individual, company, firm, corporation, or Government activity) which controls the design, characteristics, and production of the item by means of its engineering drawings, specifications and inspection requirements.
A design control or other reference number that is an item-identifying number for an item of production, or a source control reference or a specification or standard part, type, or similar reference number that is an item-identifying number for an item of supply.
The reference number is represented by technical documentation other than a drawing and the documentation was available to the RNAAC, who may or may not be the submitting activity, at the time of submission of the reference number; however, the RNAAC cannot furnish the technical documentation.
GSA, FSS/FCSC Washington, DC 20406
ISC | Originator | NIIN Status | Replaced / Replacement ISC | Replaced / Replacement Originator | Replacement NIIN Status | Replacement Date | Replaced / Replacement NSN | Decision Date |
---|---|---|---|---|---|---|---|---|
3 | TX | 0 | 1 | TX | 0 | 10 Feb 1980 | 5925012594725 | 29 Feb 1980 |
An item which, as a result of a formal item reduction study, is accepted as not authorized for procurement.
Defense Supply Center Columbus, Columbus, OH 43218
Item is active. File data coded KFD is forwarded. if this KFD data represents your item of supply, submit, if applicable, an LAD, LAU, or LCU transaction. Otherwise, use the National Stock Number (NSN) in your supply system.
An item authorized for procurement as a result of a formal item reduction study and accepted as a replacement for one or more items not authorized for procurement. In addition, in generic relationships, a code 1 item is related to a code 2 item.
Integrity | Originating | HMC | LCL | WCC | TCC | SHC | ADC | ACC | ASH | LTL | NMFC | NMFC Sub Item | UFC | Freight Description | Rail Variance |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
90 |
Tennessee Valley Authority, Chattanooga, TN 37402-2801
No Variation. NMFC and UFCC Match.
MRC | Decoded Requirement | Clear Text Reply |
---|---|---|
CPRW | Actuator Function | RESET |
ADAU | Body Height | 3.1875 INCHES NOMINAL |
ADAQ | Body Length | 6.3125 INCHES NOMINAL |
AAQL | Body Style | MULTIPOLE-SINGLE ACTUATOR TYPE |
ADAT | Body Width | 2.750 INCHES NOMINAL |
AJEC | Boss Height | 0.90625 INCHES NOMINAL |
ADTV | Case Material | PLASTIC |
CPRH | Circuit Protection Type | OVERCURRENT ALL LOCATIONS |
AEBY | Distance Between Centerlines Of Mounting Facilities Parallel To Body Length | 4.87501 INCHES NOMINAL |
FREQ | Frequency In Hertz | 60.0 ALL LOCATIONS |
CPLM | Maximum Continuous Load Current Rating Per Pole | 100.0 AMPERES AC ALL LOCATIONS AND 100.0 AMPERES DC ALL LOCATIONS |
CPRG | Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps | 10000.0 AC ALL LOCATIONS AND 5000.0 DC ALL LOCATIONS |
CPRF | Operating Voltage Type And Rating Per Pole In Volts | 240.0 AC ALL LOCATIONS AND 125.0 DC ALL LOCATIONS |
CPRR | Main Contact Tripping Mechanism Type | TRIP FREE |
CPRT | Manual Actuator Type And Quantity | 1 TOGGLE |
AKPX | Pole Quantity | 2 |
CPRQ | Reset Method | MANUAL |
FEAT | Special Features | WITHOUT LINE LUGS |
CQWN | Trip Delay Time In Seconds Per Rated Continuous Current | 89.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 370.000 MAXIMUM AT 200 PCT ALL LOCATIONS AND 35.000 MINIMUM AT 300 PCT ALL LOCATIONS AND 120.000 MAXIMUM AT 300 PCT ALL LOCATIONS AND 18.000 MINIMUM AT 400 PCT ALL LOCATIONS AND 60.000 MAXIMUM AT 400 PCT ALL LOCATIONS AND 12.000 MINIMUM AT 500 PCT ALL LOCATIONS AND 36.000 MAXIMUM AT 500 PCT ALL LOCATIONS AND 9.000 MAXIMUM AT 1000 PCT ALL LOCATIONS |
CRCF | Trip Release Ambient Temp Rating | 10.0 DEG CELSIUS MINIMUM ALL LOCATIONS AND 50.0 DEG CELSIUS MAXIMUM ALL LOCATIONS |
CPRL | Trip Release Characteristic | INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
CPRJ | Trip Release Method | THERMAL-MAGNETIC ALL LOCATIONS |
CPRN | Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent | 125.0 ALL LOCATIONS |
SUPP | Supplementary Features | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS 250.0 DC IN ADDITION TO CPRF |