5925-01-128-6405

CIRCUIT BREAKER


5925-01-128-6405 (5925011286405, 011286405)
Part Numbers (4 listings): CD3-Z369-1 | CD3Z369-1 | CD3-A2-A3-A3-90-208-CR1 | 13221E8301-1 |
Summary

FSG 59 / FSC 5925

DEMIL: A

DEMIL INT: 1

HMIC: P

Date Created: 26 Mar 1982

Unit Weight: 0.1 lbs

Unit Size: 5in x 4in x 3in

Unit Pack Cube: 0.034 cu ft

MSDS: None

Hazmat: None

Request a Quote


;



MASTER CROSS REFERENCE LIST (MCRL) | NSN 5925-01-128-6405 Submit RFQ
Manufacturer Part NumberRNCCRNVCManufacturer NameCAGE
CD3-Z369-13 - Design Control Reference2 - Production ItemEATON CORP  1W134      
CD3Z369-15 - Replaced / Discontinued2 - Production ItemHEINEMANN ELECTRIC CANADA LIMITEE  L3330      
CD3-A2-A3-A3-90-208-CR15 - Replaced / Discontinued9 - No Longer UsedEATON CORP  74193    CAGE 74193  
13221E8301-17 - Vendor Item Drawing Reference2 - Production ItemCECOM LR CENTER  97403    CAGE 97403  
Code Definitions

3 - Design Control Reference

Reference Number Category Code (DRN_2910)


Design Control Reference. The primary number used to identify an item of production or a range of items of production, by the manufacturer (individual, company, firm, corporation, or Government activity) which controls the design, characteristics, and production of the item by means of its engineering drawings, specifications and inspection requirements.

5 - Replaced / Discontinued

Reference Number Category Code (DRN_2910)


Secondary Reference. Any additional number, other than a primary number (codes 1,2,3,4) informative reference (code 6) or vendor item drawing reference (code 7) assigned to an item of production or supply by a commercial or Government organization, which represents the same item of production or supply to which the National Stock Number (NSN) was assigned. The reference number may have had an RNCC of 1, 2, 3, 4 or 7 but has since been replaced in the item-of-supply concept of the NSN by another primary number.

7 - Vendor Item Drawing Reference

Reference Number Category Code (DRN_2910)


Vendor Item Drawing Reference (formerly Specification Control Reference). The number assigned by a design activity to a drawing that is not item-identifying, but which delineates existing commercial or vendor-developed items meeting all engineering and test requirements specified, without imposing additional test/engineering requirements not normally provided by the vendor(s). Includes only those drawings which meet the definition for Vendor Item Drawing in MIL-STD 100. Vendor Item Drawing References are administrative control numbers and shall not be used as part identification numbers.

2 - Production Item

Reference Number Variation Code (DRN_4780)


A design control or other reference number that is an item-identifying number for an item of production, or a source control reference or a specification or standard part, type, or similar reference number that is an item-identifying number for an item of supply.

9 - No Longer Used

Reference Number Variation Code (DRN_4780)


A specification, standard, or other reference number which is superseded, canceled, obsolete or discontinued and is coded Reference Number Category Code (RNCC) 5; a reference number for information only coded RNCC 6; or a reference number coded RNCC D.


FLIS - SEG A - IDENTIFICATION | NSN 5925-01-128-6405 Submit RFQ
FSGFSCNIINFIIGINCCRITICALITYTYPE OF ITEMMRCDEMILHMICEDCPMICADPECDATE CREATED
595925011286405A030A000136X1APA026 Mar 1982
Code Definitions

59

Federal Supply Group (FSG_3994/FSC_WI_FSG_3996)


Electrical and Electronic Equipment Components

5925

Federal Supply Class (FSC_3994/FSC_WI_FSC_3996)


Circuit Breakers

011286405

National Item Identification Number (NCB_CD_4130/I_I_NBR_4131)


NSN 5925-01-128-6405

A030A0

Federal Item Identification Guide (FIIG_4065)

00136

Item Naming Code (INC_4080)

26 Mar 1982

NIIN Assignment Date (DT_NIIN_ASGMT_2180)

X

Item Criticality (CRITL_CD_FIIG_3843)


The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.

1

Type of Item Identification (TYP_II_4820)


Full Descriptive Item Identification

A

Demilitarization Code (DEMIL_CD_0167)


Non-MLI/ Non-SLI — Demilitarization not required.

P

Hazardous Material Indicator Code (HMIC_0865)


Indicates there is no information in the HMIRS; however, the NSN is in a FSC in Table II of Federal Standard 313 and a MSDS may be required by the user. The requirement for a MSDS is dependent on a hazard determination of the supplier or the intended end use of the product.

A

Precious Metals Indicator Code (PMIC_0802)


Item does not contain Precious Metal.

0

ADPE Identification Code (ADPEC_0801)


Represents items with no ADP components. NOTE: Codes 1 through 6 are only to be used when the item is Automatic Data Processing Equipment (ADPE) in its entirety and is limited to the type meeting only one of the definitions for codes 1 through 6. (See code 9)


FLIS - SEG B - MOE RULE DATA | NSN 5925-01-128-6405 Submit RFQ
MOE RuleFormer MOEAMCAMSCNIMSCIMCIMC ActivityAACDSORCollaboratorsReceiversEffective Date
A918A1963CZAJAZ1 Aug 2006
FXGXFXTX3CZSX1 Aug 2006
MC49MC133CZPA1 Aug 2006
N9BN3CZGHGTHD1 Aug 2006
Code Definitions

3

Acquisition Method Code (AMC_2871)


Acquire directly from the actual manufacturer, whether or not the prime contractor is the actual manufacturer.

C

Acquisition Method Suffix Code (AMSC_2876)


This part requires engineering source approval by the design control activity in order to maintain the quality of the part. An alternate source must qualify in accordance with the design control activity's procedures, as approved by the cognizant Government engineering activity. Valid AMCs: 1, 2, 3, 4 and 5.

Z

Item Management Code (IMC_2744)


Integrated Management: Relinquishment of Service management of an item in designated commodity oriented Federal Supply Classes to the IMM (FSC manager) for management.

AJ

Item Management Coding Activity (IMC_ACTY_2748)


U.S. Army Soldier's Biological and Chemical, Command, Natick, MA 01760

SX

Item Management Coding Activity (IMC_ACTY_2748)


Oklahoma City Air Logistics Center, Tinker AFB, OK 73145-3043

PA

Item Management Coding Activity (IMC_ACTY_2748)


Marine Corps Logistics Base, Albany, GA 31704-1128

GH

Item Management Coding Activity (IMC_ACTY_2748)


Naval Inventory Control Point, Mechanicsburg, PA 17055-0788

HDCollaborators

Supplementary Collaborators (SUPPLM_COLLBR_2533)


Naval Inventory Control Point, Mechanicsburg, PA 17055-0788

AZ

Supplementary Receivers (SUPPLM_RCVR_2534)


U.S. Army Tank-Automotive and Armaments, Command, Warren, MI 48397-5000


FLIS - SEG C - REFERENCE NUMBER | NSN 5925-01-128-6405 Submit RFQ
RNFCRNCCRNVCDACRNAACRNSCRNJCSADCMSDSHCCReference NumberCAGE
32EZZCD3-Z369-1  1W134  
525ZZCD3Z369-1  L3330  
59EAJCD3-A2-A3-A3-90-208-CR1  74193   CAGE/74193
721CT13221E8301-1  97403   CAGE/97403
Code Definitions

3

Reference Number Category Code (RNCC_2910)


Design Control Reference. The primary number used to identify an item of production or a range of items of production, by the manufacturer (individual, company, firm, corporation, or Government activity) which controls the design, characteristics, and production of the item by means of its engineering drawings, specifications and inspection requirements.

2

Reference Number Variation Code (RNVC_4780)


A design control or other reference number that is an item-identifying number for an item of production, or a source control reference or a specification or standard part, type, or similar reference number that is an item-identifying number for an item of supply.

E

Document Availability Code (DAC_2640)


The reference number is represented by engineering data other than an engineering drawing. The data is available for unlimited use and will be furnished by the activity identified by the RNAAC upon request.

ZZ

Reference Number Action Activity Code (RNAAC_2900)


USA

5

Reference Number Category Code (RNCC_2910)


Secondary Reference. Any additional number, other than a primary number (codes 1,2,3,4) informative reference (code 6) or vendor item drawing reference (code 7) assigned to an item of production or supply by a commercial or Government organization, which represents the same item of production or supply to which the National Stock Number (NSN) was assigned. The reference number may have had an RNCC of 1, 2, 3, 4 or 7 but has since been replaced in the item-of-supply concept of the NSN by another primary number.

5

Document Availability Code (DAC_2640)


The reference number is represented by a drawing, but the drawing was not available to the RNAAC, who may or may not be the submitting activity, at the time of submission of the reference number.

9

Reference Number Variation Code (RNVC_4780)


A specification, standard, or other reference number which is superseded, canceled, obsolete or discontinued and is coded Reference Number Category Code (RNCC) 5; a reference number for information only coded RNCC 6; or a reference number coded RNCC D.

AJ

Reference Number Action Activity Code (RNAAC_2900)


U.S. Army Soldier's Biological and Chemical, Command, Natick, MA 01760

7

Reference Number Category Code (RNCC_2910)


Vendor Item Drawing Reference (formerly Specification Control Reference). The number assigned by a design activity to a drawing that is not item-identifying, but which delineates existing commercial or vendor-developed items meeting all engineering and test requirements specified, without imposing additional test/engineering requirements not normally provided by the vendor(s). Includes only those drawings which meet the definition for Vendor Item Drawing in MIL-STD 100. Vendor Item Drawing References are administrative control numbers and shall not be used as part identification numbers.

1

Document Availability Code (DAC_2640)


The reference number is represented by a drawing and the drawing was available to the RNAAC, who may or may not be the submitting activity, at the time of submission of the reference number. The RNAAC will furnish the drawing upon request.

CT

Reference Number Action Activity Code (RNAAC_2900)


U.S. Army Aviation and Missile Command (AIR) Redstone Arsenal, AL 35898-5230


FLIS - SEG E - ITEM STANDARDIZATION DATA | NSN 5925-01-128-6405 Submit RFQ
ISCOriginatorNIIN StatusReplaced / Replacement ISCReplaced / Replacement OriginatorReplacement NIIN StatusReplacement DateReplaced / Replacement NSNDecision Date
597026 Mar 1982
Code Definitions

5

Item Standardization Code (ISC_2650)


An item authorized for procurement that has not yet been subject to item standardization.

97

Originator of Standardization Decision (ORG_STDZN_DEC_9325)


DLIS-LFF, Battle Creek, MI 49037-3084

0

NIIN Status Code (NIIN_STAT_CD_2670)


Item is active. File data coded KFD is forwarded. if this KFD data represents your item of supply, submit, if applicable, an LAD, LAU, or LCU transaction. Otherwise, use the National Stock Number (NSN) in your supply system.

26 Mar 1982

Standardization Decision Date (DT_STDZN_DEC_2300)


FLIS - SEG G - FREIGHT DATA | NSN 5925-01-128-6405 Submit RFQ
IntegrityOriginatingHMCLCLWCCTCCSHCADCACCASHLTLNMFCNMFC Sub ItemUFCFreight DescriptionRail Variance
CT658Z9AHZP061300X34410CIRCUIT-BREAKER-SWITCH-NOI
Code Definitions

CT

Originating Activity Code (ORIG_ACTY_CD_4210)


U.S. Army Aviation and Missile Command (AIR) Redstone Arsenal, AL 35898-5230

658

Water Commodity Code (WRT_CMDTY_CD_9275)


Electical Appliances, Small

Z

Type Cargo Code (TYPE_CGO_CD_9260)


No special type of cargo code applicable

9

Special Handling Code (SP_HDLG_CD_9240)


No special handling required

A

Air Dimension Code (AIR_DIM_CD_9220)


Shipment is not a consolidation and does not exceed 72 inches in any dimension.

H

Air Commodity Code (AIR_CMTY_HDLG_9215)


Signal Corps supplies and equipment, including radio equipment and supplies, communications equipment and supplies, electrical equipment and supplies, etc.

Z

Air Special Handling Code (AIR_CMTY_HDLG_9215)


No special handling required.

P

Less Than Truckload (CLAS_RTNG_CD_2770)


77.5

061300

National Motor Freight Classification Number (NMFC Item Number) (NMFC_2850)

X

NMFC Sub Item Number (SUB_ITM_NBR_0861)

34410

Uniform Freight Classification (UFC_CD_MODF_3040)

CIRCUIT-BREAKER-SWITCH-NOI

Freight Description (FRT_DESC_4020)

Rail Variance

Rail Variance (RAIL_VARI_CD_4760)


No Variation. NMFC and UFCC Match.


FLIS - SEG H - MANAGEMENT DATA | NSN 5925-01-128-6405 Submit RFQ
Unit PriceMOESOSAACCIICQUPReparabilityUISLC
DASMSHU1ZEA0
DFSMSHU1NEA0
DMSMSHU1ZEA0
DNSMSHU1EA0
DSSMSHU1NEA0
Code Definitions

SMS

Source of Supply (SOS_CD_3690) or Source of Supply Modifier (SOSM_CD_2948)


Defense Logistics Agency, Enterprise Business Systems

H

Acquisition Advice Code (AAC_2507)


DIRECT DELIVERY UNDER A CENTRAL CONTRACT # (VENDOR STOCKED) Issue, transfer or shipment is not subject to specialized controls other than those imposed by IMM/Service/Agency supply policy. 1. The item is centrally managed and procured. 2. Normal issue is by direct shipment from the vendor to the user at the order of the ICP or IMM. However, orders may be shipped from stock by ICP or IMM distribution facilities when the vendor's minimum order quantity is not met, or when stocks are being drawn down. 3. Requisitions and fund citations will be submitted in accordance with IMM/Service/Agency Requisitioning Procedures. 4. Generally delivery will be made within applicable Service/Agency guidelines addressing customer required timeframe.

U

Controlled Item Inventory Code (CIIC_2863)


Unclassified

1

Quantity Unit Pack (QUP_6106)


1

Z

Reparability Code (REP_CD_DLA_2934 / REP_CD_CG_0709 / ERRC_CD_AF_2655 / RECOV_CD_MC_2891 / RECOV_CD_AR_2892 / MAT_CTL_NVY_2832)


ARMY: This is a nonreparable item. If condemned or economically unserviceable, then dispose at the level authorized replace the item; MARINE CORPS: Nonreparable item. When unserviceable, condemn and dispose at the level indicated by the first digit of the maintenance code; NAVY: Special Program Consumables

EA

Unit of Issue (UI_3050)


Each - A numeric quantity of one item of supply. Do not use if a more specific term applies, such as kit, set, assortment, assembly, group, sheet, plate, strip or length.

0

Shelf Life Code (SLC_2943)


TYPE I or TYPE II (Non-Deteriorative/No Shelf-Life) - An individual item of supply which is determined through an evaluation of technical test data and/or actual experience to be an item with a definite non-extendible period of shelf-life OR An individual item of supply having an assigned shelf-life time period that may be extended after completion of inspection/test/restorative action.

N

Reparability Code (REP_CD_DLA_2934 / REP_CD_CG_0709 / ERRC_CD_AF_2655 / RECOV_CD_MC_2891 / RECOV_CD_AR_2892 / MAT_CTL_NVY_2832)


AIR FORCE ERRC XB3: Stock Fund (Except Munitions); DLA: This item has been reviewed and a determination made that the item cannot or should not be restored to a serviceable condition from an unserviceable condition; NAVY: 1I cog not stocked print on demand flat forms

DA

Service / Agency Code (MOE_CD_2833)


Department of the Army

DF

Service / Agency Code (MOE_CD_2833)


Department of the Air Force

DM

Service / Agency Code (MOE_CD_2833)


U.S. Marine Corps

DN

Service / Agency Code (MOE_CD_2833)


Department of the Navy

DS

Service / Agency Code (MOE_CD_2833)


Defense Logistics Agency


FLIS - SEG W - PACKAGING DATA | NSN 5925-01-128-6405 Submit RFQ
SourcePICA / SICAPackaging CategoryStoragePreservationClean/DryINT QtyUnit WeightUnit SizeUnit Pack CubeItem WeightItem Dims
PP411AAA0.1 lbs5in x 4in x 3in0.034 cu ft
Preservation MaterialWrapping MaterialCushioning / DunnageCushioning ThicknessUnit ContainerIntermediate ContainerUnit Container LevelSpecial MarkingLevel A PackingLevel B PackingMinimal PackingOptional Procedure
0000NAXD3DO00QQO
Code Definitions

P

Packaging Data Source Code (PK_DTA_SRC_CD_5148)


Primary Inventory Control Activity (PICA)

P

Primary / Secondary Inventory Control Code (PICA_SICA_IND_5099)


Primary Inventory Control Activity (PICA)

41

Method of Preservation Code (MTHD_PRSRV_CD_5160)


Watervaporproof bag, sealed

1

Cleaning and Drying Procedure Code (CLNG_DRY_PRC_5161)


Any suitable process that is not injurious to the item.

AAA

Intermediate Container Quantity (INTMD_CTN_QTY_5152)

0.1 lbs

Unit Pack Weight (UP_WT_5153)

5in x 4in x 3in

Unit Pack Size (UP_SZ_5154)

0.034 cu ft

Unit Pack Cube (UP_CU_5155)

00

Preservation Material Code (PRSRV_MAT_CD_5162)


No requirement

00

Wrapping Material Code (WRAP_MAT_CD_5163)


No requirement

NA

Cushioning and Dunnage Material Code (CUSH_DUN_MAT_5164)


PPP-C-795, cellular plastic film cushioning; or A-A-3129, open cell plastic cushioning; or PPP-C-1797, polypropylene foam cushioning; or A-A-59136, polyethylene foam cushioning

X

Thickness of Cushioning or Dunnage Code (THK_CUSH_DUN_5165)


As required to protect the item or elements of the package

D3

Unit Container Code (UNIT_CTNR_CD_5166)


PPP-B-566, PPP-B-676, or ASTM-D5118, folding, setup or fiberboard box.

DO

Intermediate Container Code (INTMD_CTNR_CD_5167)


Any suitable fiber box included in this table may be used (see J.4.9.1).

00

Special Marking Code (SP_MKG_CD_5169)


No special marking

Q

Packing Requirement Code - For Level A (Maximum) Packing (LVL_A_PKG_CD_5170)


Packing shall be accomplished in accordance with table C.II for the packing level specified. Closure sealing and reinforcement shall be in accordance with applicable specification for shipping container.

Q

Packing Requirement Code - For Level B (Intermediate) Packing (LVL_B_PKG_CD_5171)


Packing shall be accomplished in accordance with table C-II for the packing level specified. Closure sealing and reinforcement shall be in accordance with the appropriate shipping container specification.

O

Optional Procedure Indicator Code (OPTNL_PRO_IND_5173)


Options can be exercised as to specific method of preservation or DoD approved packaging materials to be used. However, basic preservation method shall be retained, supplemental data shall be complied with, and unit package dimensions shall not be increased by more than one inch. Equal or better protection shall be given the item and there shall be no increase in the package cost.


FLIS - SEG M/V - CHARACTERISTICS DATA | NSN 5925-01-128-6405 Submit RFQ
MRCDecoded RequirementClear Text Reply
CPRWActuator FunctionTRIP-RESET
CPRXActuator Position DesignationAT EACH POLE
APNQArc Quenching MethodAIR
ADAUBody Height2.609 INCHES NOMINAL
ADAQBody Length4.750 INCHES NOMINAL
AAQLBody StyleMULTIPOLE-MULTIPLE ACTUATOR TYPE
ADATBody Width3.186 INCHES NOMINAL
AJECBoss Height0.219 INCHES NOMINAL
ADTVCase MaterialPLASTIC
AEBQCenter To Center Distance Between Terminals Parallel To Width1.026 INCHES NOMINAL
CPRHCircuit Protection TypeOVERCURRENT ALL LOCATIONS
CPRYExternal Actuator Linkage ArrangementONE, TWO, AND THREE LINKED
AFJNFragility FactorMODERATELY RUGGED
FREQFrequency In Hertz60.0 ALL LOCATIONS
CBMECubic Measure39.483 CUBIC INCHES
CPLMMaximum Continuous Load Current Rating Per Pole90.0 AMPERES AC ALL LOCATIONS
CPRGMaximum Interrupting Capacity Current Type And Rating Per Pole In Amps5000.0 AC ALL LOCATIONS
AXHRMounting Facility Type And Quantity6 THREADED HOLE
CQJXNominal Thread Size0.138 INCHES
CPRFOperating Voltage Type And Rating Per Pole In Volts208.0 AC ALL LOCATIONS
CQXFInclosure Protection Type For Which DesignedDUSTPROOF
CPSMInternal Trip Release ConfigurationSERIES TRIP ALL LOCATIONS
CPRRMain Contact Tripping Mechanism TypeTRIP FREE
CPRTManual Actuator Type And Quantity3 TOGGLE
AKPXPole Quantity3
CPRQReset MethodMANUAL
CPRLTrip Release CharacteristicTIME DELAY ALL LOCATIONS
CPRJTrip Release MethodMAGNETIC-HYDRAULIC ALL LOCATIONS
CQWNTrip Delay Time In Seconds Per Rated Continuous Current11.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 100.000 MAXIMUM AT 200 PCT ALL LOCATIONS
CPRNUltimate Trip Rating Of Continuous Current Rating Per Pole In Percent130.0 ALL LOCATIONS
BBRGStorage TypeGENERAL PURPOSE WAREHOUSE
TTQYTerminal Type And Quantity6 SCREW
THSDThread Series DesignatorUNC
CMLPThread Quantity Per Inch32


Back to Top
Back to Top