Manufacturer Part Number | RNCC | RNVC | Manufacturer Name | CAGE | |
---|---|---|---|---|---|
AM1-A3-A-5 | 3 - Design Control Reference | 9 - No Longer Used | EATON CORP | 74193 | ![]() |
Design Control Reference. The primary number used to identify an item of production or a range of items of production, by the manufacturer (individual, company, firm, corporation, or Government activity) which controls the design, characteristics, and production of the item by means of its engineering drawings, specifications and inspection requirements.
A specification, standard, or other reference number which is superseded, canceled, obsolete or discontinued and is coded Reference Number Category Code (RNCC) 5; a reference number for information only coded RNCC 6; or a reference number coded RNCC D.
FSG | FSC | NIIN | FIIG | INC | CRITICALITY | TYPE OF ITEM | MRC | DEMIL | HMIC | EDC | PMIC | ADPEC | DATE CREATED |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
59 | 5925 | 012076757 | A030A0 | 00136 | X | 1 | A | P | A | 4 May 1985 |
The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.
Full Descriptive Item Identification
Non-MLI/ Non-SLI — Demilitarization not required.
Indicates there is no information in the HMIRS; however, the NSN is in a FSC in Table II of Federal Standard 313 and a MSDS may be required by the user. The requirement for a MSDS is dependent on a hazard determination of the supplier or the intended end use of the product.
Item does not contain Precious Metal.
MOE Rule | Former MOE | AMC | AMSC | NIMSC | IMC | IMC Activity | AAC | DSOR | Collaborators | Receivers | Effective Date | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
YS01 | 1 Feb 2015 |
ISC | Originator | NIIN Status | Replaced / Replacement ISC | Replaced / Replacement Originator | Replacement NIIN Status | Replacement Date | Replaced / Replacement NSN | Decision Date |
---|---|---|---|---|---|---|---|---|
5 | 97 | 6 | 4 May 1985 |
An item authorized for procurement that has not yet been subject to item standardization.
DLIS-LFF, Battle Creek, MI 49037-3084
Item is inactive (no recorded Primary/Secondary Inventory Control Activity (PICA/SICA)). File data coded KFD is forwarded.
Integrity | Originating | HMC | LCL | WCC | TCC | SHC | ADC | ACC | ASH | LTL | NMFC | NMFC Sub Item | UFC | Freight Description | Rail Variance |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
9Z | P | 658 | Z | Z | A | H | Z | P | 061300 | X | 34410 | CIRCUIT-BREAKER-SWITCH-NOI |
DLIS-K, Battle Creek, MI 49037-3084
77.5
Electical Appliances, Small
No special type of cargo code applicable
No special handling required. Heavy Lift (HL). Five short tons (10,000 lbs) or more. Applies to any piece, package, or palletized, unitized or containerized unit (excluding SEAVAN/MILVAN). Outsized Dimensions. Dimensions of any piece, package, or palletized, unitized or containerized unit (excluding SEAVAN/MILVAN, CONEXs, and POVs) which exceed six (6) feet in any dimension.
Shipment is not a consolidation and does not exceed 72 inches in any dimension.
Signal Corps supplies and equipment, including radio equipment and supplies, communications equipment and supplies, electrical equipment and supplies, etc.
No special handling required.
No Variation. NMFC and UFCC Match.
MRC | Decoded Requirement | Clear Text Reply |
---|---|---|
CPRW | Actuator Function | TRIP-RESET |
CPRX | Actuator Position Designation | AT POLE ONE |
APNQ | Arc Quenching Method | MAGNETIC BLOWOUT |
ADAQ | Body Length | 2.490 INCHES MINIMUM AND 2.510 INCHES MAXIMUM |
AAQL | Body Style | SINGLE POLE TYPE |
ADAT | Body Width | 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM |
AJEC | Boss Height | 0.130 INCHES MINIMUM AND 0.140 INCHES MAXIMUM |
ADTV | Case Material | PLASTIC |
AEBP | Center To Center Distance Between Terminals Parallel To Length | 1.928 INCHES MINIMUM AND 1.948 INCHES MAXIMUM |
CPRH | Circuit Protection Type | OVERCURRENT SINGLE LOCATION |
AEBY | Distance Between Centerlines Of Mounting Facilities Parallel To Body Length | 2.052 INCHES MINIMUM AND 2.072 INCHES MAXIMUM |
AFJN | Fragility Factor | MODERATELY RUGGED |
FREQ | Frequency In Hertz | 60.0 SINGLE LOCATION |
CPLM | Maximum Continuous Load Current Rating Per Pole | 5.0 AMPERES AC SINGLE LOCATION |
CPRG | Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps | 1000.0 AC SINGLE LOCATION |
AXHR | Mounting Facility Type And Quantity | 2 THREADED HOLE |
AJWX | Mounting Surface To Terminal End Distance | 2.611 INCHES NOMINAL |
CQJX | Nominal Thread Size | 0.138 INCHES |
CPRF | Operating Voltage Type And Rating Per Pole In Volts | 250.0 AC SINGLE LOCATION |
CQXF | Inclosure Protection Type For Which Designed | DUSTPROOF AND FUNGUS PROOF |
CPSM | Internal Trip Release Configuration | SERIES TRIP SINGLE LOCATION |
CPRR | Main Contact Tripping Mechanism Type | TRIP FREE |
CPRT | Manual Actuator Type And Quantity | 1 TOGGLE |
AKPX | Pole Quantity | 1 |
CPRQ | Reset Method | MANUAL |
CPRL | Trip Release Characteristic | TIME DELAY SINGLE LOCATION |
CPRJ | Trip Release Method | MAGNETIC-HYDRAULIC SINGLE LOCATION |
CQWN | Trip Delay Time In Seconds Per Rated Continuous Current | 2.000 MINIMUM AT 200 PCT AND 20.000 MAXIMUM AT 200 PCT SINGLE LOCATION |
CPRN | Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent | 125.0 SINGLE LOCATION |
BBRG | Storage Type | GENERAL PURPOSE WAREHOUSE |
TTQY | Terminal Type And Quantity | 2 THREADED STUD |
THSD | Thread Series Designator | UNC |
CMLP | Thread Quantity Per Inch | 32 |