5925-01-255-3079

CIRCUIT BREAKER


5925-01-255-3079 (5925012553079, 012553079)
Part Numbers (2 listings): APL2-9433-1 | 911383-001 |
Summary

FSG 59 / FSC 5925

DEMIL: A

DEMIL INT:

HMIC: P

Date Created: 18 May 1987

MSDS: None

Hazmat: None

Request a Quote


;



MASTER CROSS REFERENCE LIST (MCRL) | NSN 5925-01-255-3079 Submit RFQ
Manufacturer Part NumberRNCCRNVCManufacturer NameCAGE
APL2-9433-13 - Design Control Reference2 - Production ItemSENSATA TECHNOLOGIES MARYLAND, INC  81541    CAGE 81541  
911383-0017 - Vendor Item Drawing Reference2 - Production ItemMOOG INC.  19156    CAGE 19156  
Code Definitions

3 - Design Control Reference

Reference Number Category Code (DRN_2910)


Design Control Reference. The primary number used to identify an item of production or a range of items of production, by the manufacturer (individual, company, firm, corporation, or Government activity) which controls the design, characteristics, and production of the item by means of its engineering drawings, specifications and inspection requirements.

7 - Vendor Item Drawing Reference

Reference Number Category Code (DRN_2910)


Vendor Item Drawing Reference (formerly Specification Control Reference). The number assigned by a design activity to a drawing that is not item-identifying, but which delineates existing commercial or vendor-developed items meeting all engineering and test requirements specified, without imposing additional test/engineering requirements not normally provided by the vendor(s). Includes only those drawings which meet the definition for Vendor Item Drawing in MIL-STD 100. Vendor Item Drawing References are administrative control numbers and shall not be used as part identification numbers.

2 - Production Item

Reference Number Variation Code (DRN_4780)


A design control or other reference number that is an item-identifying number for an item of production, or a source control reference or a specification or standard part, type, or similar reference number that is an item-identifying number for an item of supply.


FLIS - SEG A - IDENTIFICATION | NSN 5925-01-255-3079 Submit RFQ
FSGFSCNIINFIIGINCCRITICALITYTYPE OF ITEMMRCDEMILHMICEDCPMICADPECDATE CREATED
595925012553079A030A000136X46APA018 May 1987
Code Definitions

59

Federal Supply Group (FSG_3994/FSC_WI_FSG_3996)


Electrical and Electronic Equipment Components

5925

Federal Supply Class (FSC_3994/FSC_WI_FSC_3996)


Circuit Breakers

012553079

National Item Identification Number (NCB_CD_4130/I_I_NBR_4131)


NSN 5925-01-255-3079

A030A0

Federal Item Identification Guide (FIIG_4065)

00136

Item Naming Code (INC_4080)

18 May 1987

NIIN Assignment Date (DT_NIIN_ASGMT_2180)

X

Item Criticality (CRITL_CD_FIIG_3843)


The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.

4

Type of Item Identification (TYP_II_4820)


Partial Descriptive Item Identification (Type 1 Concept)

6

Reference / Partial Descriptive Method Reason Code (RPDMRC_4765)


An approved item name and FIIG may exist, but it has previously been established and documented that industry refuses to provide the technical data sufficient for preparation on a full descriptive method item identification based on policy, restricted or proprietary data rights, nonexistence of technical data, etc.

A

Demilitarization Code (DEMIL_CD_0167)


Non-MLI/ Non-SLI — Demilitarization not required.

P

Hazardous Material Indicator Code (HMIC_0865)


Indicates there is no information in the HMIRS; however, the NSN is in a FSC in Table II of Federal Standard 313 and a MSDS may be required by the user. The requirement for a MSDS is dependent on a hazard determination of the supplier or the intended end use of the product.

A

Precious Metals Indicator Code (PMIC_0802)


Item does not contain Precious Metal.

0

ADPE Identification Code (ADPEC_0801)


Represents items with no ADP components. NOTE: Codes 1 through 6 are only to be used when the item is Automatic Data Processing Equipment (ADPE) in its entirety and is limited to the type meeting only one of the definitions for codes 1 through 6. (See code 9)


FLIS - SEG B - MOE RULE DATA | NSN 5925-01-255-3079 Submit RFQ
MOE RuleFormer MOEAMCAMSCNIMSCIMCIMC ActivityAACDSORCollaboratorsReceiversEffective Date
ZK011 Feb 1996
Code Definitions

FLIS - SEG C - REFERENCE NUMBER | NSN 5925-01-255-3079 Submit RFQ
RNFCRNCCRNVCDACRNAACRNSCRNJCSADCMSDSHCCReference NumberCAGE
3259ZDAPL2-9433-1  81541   CAGE/81541
7229ZD911383-001  19156   CAGE/19156
Code Definitions

3

Reference Number Category Code (RNCC_2910)


Design Control Reference. The primary number used to identify an item of production or a range of items of production, by the manufacturer (individual, company, firm, corporation, or Government activity) which controls the design, characteristics, and production of the item by means of its engineering drawings, specifications and inspection requirements.

2

Reference Number Variation Code (RNVC_4780)


A design control or other reference number that is an item-identifying number for an item of production, or a source control reference or a specification or standard part, type, or similar reference number that is an item-identifying number for an item of supply.

5

Document Availability Code (DAC_2640)


The reference number is represented by a drawing, but the drawing was not available to the RNAAC, who may or may not be the submitting activity, at the time of submission of the reference number.

9Z

Reference Number Action Activity Code (RNAAC_2900)


DLIS-K, Battle Creek, MI 49037-3084

D

Reference Number Status Code (RNSC_2923)


Procurement authority of the manufacturer and reference number have not yet been checked. NOTE: This code is to be allocated to reference numbers still requiring checks on procurement authority.

7

Reference Number Category Code (RNCC_2910)


Vendor Item Drawing Reference (formerly Specification Control Reference). The number assigned by a design activity to a drawing that is not item-identifying, but which delineates existing commercial or vendor-developed items meeting all engineering and test requirements specified, without imposing additional test/engineering requirements not normally provided by the vendor(s). Includes only those drawings which meet the definition for Vendor Item Drawing in MIL-STD 100. Vendor Item Drawing References are administrative control numbers and shall not be used as part identification numbers.

2

Document Availability Code (DAC_2640)


The reference number is represented by a drawing and the drawing was available to the RNAAC, who may or may not be the submitting activity, at the time of submission of the reference number; however, the RNAAC cannot furnish the drawing.


FLIS - SEG E - ITEM STANDARDIZATION DATA | NSN 5925-01-255-3079 Submit RFQ
ISCOriginatorNIIN StatusReplaced / Replacement ISCReplaced / Replacement OriginatorReplacement NIIN StatusReplacement DateReplaced / Replacement NSNDecision Date
597018 May 1987
Code Definitions

5

Item Standardization Code (ISC_2650)


An item authorized for procurement that has not yet been subject to item standardization.

97

Originator of Standardization Decision (ORG_STDZN_DEC_9325)


DLIS-LFF, Battle Creek, MI 49037-3084

0

NIIN Status Code (NIIN_STAT_CD_2670)


Item is active. File data coded KFD is forwarded. if this KFD data represents your item of supply, submit, if applicable, an LAD, LAU, or LCU transaction. Otherwise, use the National Stock Number (NSN) in your supply system.

18 May 1987

Standardization Decision Date (DT_STDZN_DEC_2300)


FLIS - SEG G - FREIGHT DATA | NSN 5925-01-255-3079 Submit RFQ
IntegrityOriginatingHMCLCLWCCTCCSHCADCACCASHLTLNMFCNMFC Sub ItemUFCFreight DescriptionRail Variance
ZK
Code Definitions

ZK

Originating Activity Code (ORIG_ACTY_CD_4210)


United Kingdom

Rail Variance

Rail Variance (RAIL_VARI_CD_4760)


No Variation. NMFC and UFCC Match.


FLIS - SEG M/V - CHARACTERISTICS DATA | NSN 5925-01-255-3079 Submit RFQ
MRCDecoded RequirementClear Text Reply
CPLMMaximum Continuous Load Current Rating Per Pole20.0 AMPERES DC SINGLE LOCATION
CPRFOperating Voltage Type And Rating Per Pole In Volts50.0 DC SINGLE LOCATION
CPRRMain Contact Tripping Mechanism TypeTRIP FREE
AKPXPole Quantity1
CQWNTrip Delay Time In Seconds Per Rated Continuous Current0.500 MINIMUM AT 125 PCT SINGLE LOCATION AND 6.500 MAXIMUM AT 125 PCT SINGLE LOCATION AND 0.300 MINIMUM AT 150 PCT SINGLE LOCATION AND 3.000 MAXIMUM AT 150 PCT SINGLE LOCATION AND 0.130 MINIMUM AT 200 PCT SINGLE LOCATION AND 1.200 MAXIMUM AT 200 PCT SINGLE LOCATION AND 0.031 MINIMUM AT 400 PCT SINGLE LOCATION AND 0.220 MAXIMUM AT 400 PCT SINGLE LOCATION AND 0.031 MINIMUM AT 600 PCT SINGLE LOCATION AND 0.220 MAXIMUM AT 600 PCT SINGLE LOCATION AND 0.0110 MINIMUM AT 800 PCT SINGLE LOCATION AND 0.110 MAXIMUM AT 800 PCT SINGLE LOCATION AND 0.004 MINIMUM AT 1000 PCT SINGLE LOCATION AND 0.050 MAXIMUM AT 1000 PCT SINGLE LOCATION
CPRLTrip Release CharacteristicTIME DELAY SINGLE LOCATION
CPRJTrip Release MethodMAGNETIC SINGLE LOCATION


Back to Top