Manufacturer Part Number | RNCC | RNVC | Manufacturer Name | CAGE | |
---|---|---|---|---|---|
JA2-A3A3-A-10-2 | 3 - Design Control Reference | 9 - No Longer Used | EATON CORP | 74193 | ![]() |
Design Control Reference. The primary number used to identify an item of production or a range of items of production, by the manufacturer (individual, company, firm, corporation, or Government activity) which controls the design, characteristics, and production of the item by means of its engineering drawings, specifications and inspection requirements.
A specification, standard, or other reference number which is superseded, canceled, obsolete or discontinued and is coded Reference Number Category Code (RNCC) 5; a reference number for information only coded RNCC 6; or a reference number coded RNCC D.
FSG | FSC | NIIN | FIIG | INC | CRITICALITY | TYPE OF ITEM | MRC | DEMIL | HMIC | EDC | PMIC | ADPEC | DATE CREATED |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
59 | 5925 | 012650827 | A030A0 | 00136 | X | 1 | A | P | U | 9 Oct 1987 |
The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.
Full Descriptive Item Identification
Non-MLI/ Non-SLI — Demilitarization not required.
Indicates there is no information in the HMIRS; however, the NSN is in a FSC in Table II of Federal Standard 313 and a MSDS may be required by the user. The requirement for a MSDS is dependent on a hazard determination of the supplier or the intended end use of the product.
Precious Metal Content is unknown.
MOE Rule | Former MOE | AMC | AMSC | NIMSC | IMC | IMC Activity | AAC | DSOR | Collaborators | Receivers | Effective Date | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
ZC01 | 1 Apr 1991 |
RNFC | RNCC | RNVC | DAC | RNAAC | RNSC | RNJC | SADC | MSDS | HCC | Reference Number | CAGE | |
---|---|---|---|---|---|---|---|---|---|---|---|---|
3 | 9 | E | TX | D | JA2-A3A3-A-10-2 | 74193 | ![]() |
Design Control Reference. The primary number used to identify an item of production or a range of items of production, by the manufacturer (individual, company, firm, corporation, or Government activity) which controls the design, characteristics, and production of the item by means of its engineering drawings, specifications and inspection requirements.
A specification, standard, or other reference number which is superseded, canceled, obsolete or discontinued and is coded Reference Number Category Code (RNCC) 5; a reference number for information only coded RNCC 6; or a reference number coded RNCC D.
The reference number is represented by engineering data other than an engineering drawing. The data is available for unlimited use and will be furnished by the activity identified by the RNAAC upon request.
Defense Supply Center Columbus, Columbus, OH 43218
Procurement authority of the manufacturer and reference number have not yet been checked. NOTE: This code is to be allocated to reference numbers still requiring checks on procurement authority.
ISC | Originator | NIIN Status | Replaced / Replacement ISC | Replaced / Replacement Originator | Replacement NIIN Status | Replacement Date | Replaced / Replacement NSN | Decision Date |
---|---|---|---|---|---|---|---|---|
5 | 97 | 0 | 9 Oct 1987 |
An item authorized for procurement that has not yet been subject to item standardization.
DLIS-LFF, Battle Creek, MI 49037-3084
Item is active. File data coded KFD is forwarded. if this KFD data represents your item of supply, submit, if applicable, an LAD, LAU, or LCU transaction. Otherwise, use the National Stock Number (NSN) in your supply system.
Integrity | Originating | HMC | LCL | WCC | TCC | SHC | ADC | ACC | ASH | LTL | NMFC | NMFC Sub Item | UFC | Freight Description | Rail Variance |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
ZC |
Canada
No Variation. NMFC and UFCC Match.
MRC | Decoded Requirement | Clear Text Reply |
---|---|---|
CPRW | Actuator Function | TRIP-RESET |
CPRX | Actuator Position Designation | AT EACH POLE |
APNQ | Arc Quenching Method | MAGNETIC BLOWOUT |
ADAQ | Body Length | 1.985 INCHES MINIMUM AND 2.015 INCHES MAXIMUM |
AAQL | Body Style | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
ADAT | Body Width | 1.468 INCHES MINIMUM AND 1.532 INCHES MAXIMUM |
AJEC | Boss Height | 0.125 INCHES MINIMUM AND 0.135 INCHES MAXIMUM |
ADTV | Case Material | PLASTIC |
AEBQ | Center To Center Distance Between Terminals Parallel To Width | 0.745 INCHES MINIMUM AND 0.755 INCHES MAXIMUM |
AEBP | Center To Center Distance Between Terminals Parallel To Length | 1.555 INCHES MINIMUM AND 1.565 INCHES MAXIMUM |
CPRH | Circuit Protection Type | OVERCURRENT ALL LOCATIONS |
AEBY | Distance Between Centerlines Of Mounting Facilities Parallel To Body Length | 1.655 INCHES MINIMUM AND 1.665 INCHES MAXIMUM |
AEHA | Distance Between Centerlines Of Mounting Facilities Parallel To Body Width | 0.745 INCHES MINIMUM AND 0.755 INCHES MAXIMUM |
CPRY | External Actuator Linkage Arrangement | ONE AND TWO LINKED |
AFJN | Fragility Factor | MODERATELY RUGGED |
FREQ | Frequency In Hertz | 60.0 ALL LOCATIONS |
CPLM | Maximum Continuous Load Current Rating Per Pole | 10.0 AMPERES AC ALL LOCATIONS |
CPRG | Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps | 1000.0 AC ALL LOCATIONS |
AXHR | Mounting Facility Type And Quantity | 4 THREADED HOLE |
AJWX | Mounting Surface To Terminal End Distance | 1.835 INCHES MINIMUM AND 1.845 INCHES MAXIMUM |
CQJX | Nominal Thread Size | 0.138 INCHES |
CPRF | Operating Voltage Type And Rating Per Pole In Volts | 250.0 AC ALL LOCATIONS |
CQXF | Inclosure Protection Type For Which Designed | DUSTPROOF |
CPSM | Internal Trip Release Configuration | SERIES TRIP ALL LOCATIONS |
CPRR | Main Contact Tripping Mechanism Type | TRIP FREE |
CPRT | Manual Actuator Type And Quantity | 2 TOGGLE |
AKPX | Pole Quantity | 2 |
CPRQ | Reset Method | MANUAL |
THSD | Thread Series Designator | UNC |
CQWN | Trip Delay Time In Seconds Per Rated Continuous Current | 2.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 20.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CPRL | Trip Release Characteristic | TIME DELAY ALL LOCATIONS |
CPRJ | Trip Release Method | MAGNETIC-HYDRAULIC ALL LOCATIONS |
CPRN | Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent | 125.0 ALL LOCATIONS |
BBRG | Storage Type | GENERAL PURPOSE WAREHOUSE |
TTQY | Terminal Type And Quantity | 4 TAB, SOLDER LUG |
CMLP | Thread Quantity Per Inch | 32 |