Manufacturer Part Number | RNCC | RNVC | Manufacturer Name | CAGE | |
---|---|---|---|---|---|
54E4750 | 3 - Design Control Reference | 9 - No Longer Used | WESTINGHOUSE ELECTRIC CORP | 11660 | ![]() |
Design Control Reference. The primary number used to identify an item of production or a range of items of production, by the manufacturer (individual, company, firm, corporation, or Government activity) which controls the design, characteristics, and production of the item by means of its engineering drawings, specifications and inspection requirements.
A specification, standard, or other reference number which is superseded, canceled, obsolete or discontinued and is coded Reference Number Category Code (RNCC) 5; a reference number for information only coded RNCC 6; or a reference number coded RNCC D.
FSG | FSC | NIIN | FIIG | INC | CRITICALITY | TYPE OF ITEM | MRC | DEMIL | HMIC | EDC | PMIC | ADPEC | DATE CREATED |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
59 | 5925 | 013243468 | A030A0 | 00136 | X | K | A | P | A | 15 Aug 1990 |
The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.
Full Descriptive - Reference Item Identification
Non-MLI/ Non-SLI — Demilitarization not required.
Indicates there is no information in the HMIRS; however, the NSN is in a FSC in Table II of Federal Standard 313 and a MSDS may be required by the user. The requirement for a MSDS is dependent on a hazard determination of the supplier or the intended end use of the product.
Item does not contain Precious Metal.
MOE Rule | Former MOE | AMC | AMSC | NIMSC | IMC | IMC Activity | AAC | DSOR | Collaborators | Receivers | Effective Date | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
C056 | C165 | 3 | P | 1 Jun 2010 |
Acquire directly from the actual manufacturer, whether or not the prime contractor is the actual manufacturer.
The rights to use the data needed to purchase this part from additional sources are not owned by the Government and cannot be purchased. Valid AMCs: 1, 2, 3, 4 and 5.
ISC | Originator | NIIN Status | Replaced / Replacement ISC | Replaced / Replacement Originator | Replacement NIIN Status | Replacement Date | Replaced / Replacement NSN | Decision Date |
---|---|---|---|---|---|---|---|---|
5 | 97 | 0 | 15 Aug 1990 |
An item authorized for procurement that has not yet been subject to item standardization.
DLIS-LFF, Battle Creek, MI 49037-3084
Item is active. File data coded KFD is forwarded. if this KFD data represents your item of supply, submit, if applicable, an LAD, LAU, or LCU transaction. Otherwise, use the National Stock Number (NSN) in your supply system.
Integrity | Originating | HMC | LCL | WCC | TCC | SHC | ADC | ACC | ASH | LTL | NMFC | NMFC Sub Item | UFC | Freight Description | Rail Variance |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
No Variation. NMFC and UFCC Match.
Commanding Officer, USCG Surface Force Logistics Center, Code 028, Mil Stop 25, 2401 Hawkins Point Road, Baltimore, MD 21226-5000
INSURANCE/NUMERIC STOCKAGE OBJECTIVE ITEM. Items which may be required occasionally or intermittently, and prudence requires that a nominal quantity of materiel be stocked due to the essentiality or the lead time of the item. 1. The item is centrally managed, stocked, and issued. 2. Requisitions will be submitted in accordance with IMM/Service requisitioning procedures.
Unclassified
1
ARMY: Item requires special handling or condemnation procedures for specific reasons, such as precious metal content, high dollar value, critical material, or hazardous materiel. Refer to appropriate manuals or directives for specific instructions; MARINE CORPS: Item requires special handling/or condemnation procedures because of specific reasons (i.e., precious metal content, high dollar value, critical material, or hazardous material). Refer to appropriate manuals/directives for specific instructions; NAVY: Field Activity Control Items
Each - A numeric quantity of one item of supply. Do not use if a more specific term applies, such as kit, set, assortment, assembly, group, sheet, plate, strip or length.
TYPE I or TYPE II (Non-Deteriorative/No Shelf-Life) - An individual item of supply which is determined through an evaluation of technical test data and/or actual experience to be an item with a definite non-extendible period of shelf-life OR An individual item of supply having an assigned shelf-life time period that may be extended after completion of inspection/test/restorative action.
U.S. Coast Guard
MRC | Decoded Requirement | Clear Text Reply |
---|---|---|
CPRW | Actuator Function | TRIP-RESET |
ADAU | Body Height | 4.062 INCHES NOMINAL |
ADAQ | Body Length | 10.125 INCHES NOMINAL |
AAQL | Body Style | MULTIPOLE-SINGLE ACTUATOR TYPE |
ADAT | Body Width | 5.490 INCHES NOMINAL |
AJEC | Boss Height | 0.188 INCHES NOMINAL |
ADTV | Case Material | PLASTIC |
AEBQ | Center To Center Distance Between Terminals Parallel To Width | 1.719 INCHES NOMINAL |
AEBP | Center To Center Distance Between Terminals Parallel To Length | 8.975 INCHES NOMINAL |
CPRH | Circuit Protection Type | OVERCURRENT ALL LOCATIONS |
AEBY | Distance Between Centerlines Of Mounting Facilities Parallel To Body Length | 8.350 INCHES NOMINAL |
AEHA | Distance Between Centerlines Of Mounting Facilities Parallel To Body Width | 1.719 INCHES NOMINAL |
AGAV | End Item Identification | SHIPS SERVICE GENERATOR AND POWER SUPPLY ONBOARD 400 FT WAGB C.G. VESSELS |
FREQ | Frequency In Hertz | 60.0 ALL LOCATIONS |
CPLM | Maximum Continuous Load Current Rating Per Pole | 225.0 AMPERES AC ALL LOCATIONS AND 225.0 AMPERES DC ALL LOCATIONS |
CPRG | Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps | 25000.0 AC ALL LOCATIONS AND 10000.0 DC ALL LOCATIONS |
AXHR | Mounting Facility Type And Quantity | 4 UNTHREADED HOLE |
CPRF | Operating Voltage Type And Rating Per Pole In Volts | 600.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS |
CPRR | Main Contact Tripping Mechanism Type | TRIP FREE |
CPRT | Manual Actuator Type And Quantity | 1 TOGGLE |
AKPX | Pole Quantity | 3 |
CPRQ | Reset Method | MANUAL |
FEAT | Special Features | 120.0 VOLT UNDER VOLTAGE RELEASE INCLUDED,60.0 IN. WIRE LEADS INCLUDED WITH ITEM |
CQWN | Trip Delay Time In Seconds Per Rated Continuous Current | 150.000 NOMINAL AT 150 PCT ALL LOCATIONS |
CPRL | Trip Release Characteristic | TIME DELAY ALL LOCATIONS |
CPRJ | Trip Release Method | THERMAL-MAGNETIC ALL LOCATIONS |
CRCF | Trip Release Ambient Temp Rating | 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
CPRN | Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent | 115.0 ALL LOCATIONS |
AEBV | Unthreaded Mounting Hole Diameter | 0.281 INCHES NOMINAL |
TTQY | Terminal Type And Quantity | 6 SCREW |