5925-01-483-0111

CIRCUIT BREAKER


5925-01-483-0111 (5925014830111, 014830111)
Part Number (1 listing): IEG6-1REC4-61-15.0-21-V
Summary

FSG 59 / FSC 5925

DEMIL: A

DEMIL INT: 1

HMIC: P

Date Created: 13 Mar 2001

MSDS: None

Hazmat: None

Request a Quote


;



MASTER CROSS REFERENCE LIST (MCRL) | NSN 5925-01-483-0111 Submit RFQ
Manufacturer Part NumberRNCCRNVCManufacturer NameCAGE
IEG6-1REC4-61-15.0-21-V3 - Design Control Reference2 - Production ItemSENSATA TECHNOLOGIES MARYLAND, INC  81541    CAGE 81541  
Code Definitions

3 - Design Control Reference

Reference Number Category Code (DRN_2910)


Design Control Reference. The primary number used to identify an item of production or a range of items of production, by the manufacturer (individual, company, firm, corporation, or Government activity) which controls the design, characteristics, and production of the item by means of its engineering drawings, specifications and inspection requirements.

2 - Production Item

Reference Number Variation Code (DRN_4780)


A design control or other reference number that is an item-identifying number for an item of production, or a source control reference or a specification or standard part, type, or similar reference number that is an item-identifying number for an item of supply.


FLIS - SEG A - IDENTIFICATION | NSN 5925-01-483-0111 Submit RFQ
FSGFSCNIINFIIGINCCRITICALITYTYPE OF ITEMMRCDEMILHMICEDCPMICADPECDATE CREATED
595925014830111A030A000136X46APAA013 Mar 2001
Code Definitions

59

Federal Supply Group (FSG_3994/FSC_WI_FSG_3996)


Electrical and Electronic Equipment Components

5925

Federal Supply Class (FSC_3994/FSC_WI_FSC_3996)


Circuit Breakers

014830111

National Item Identification Number (NCB_CD_4130/I_I_NBR_4131)


NSN 5925-01-483-0111

A030A0

Federal Item Identification Guide (FIIG_4065)

00136

Item Naming Code (INC_4080)

13 Mar 2001

NIIN Assignment Date (DT_NIIN_ASGMT_2180)

X

Item Criticality (CRITL_CD_FIIG_3843)


The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.

4

Type of Item Identification (TYP_II_4820)


Partial Descriptive Item Identification (Type 1 Concept)

6

Reference / Partial Descriptive Method Reason Code (RPDMRC_4765)


An approved item name and FIIG may exist, but it has previously been established and documented that industry refuses to provide the technical data sufficient for preparation on a full descriptive method item identification based on policy, restricted or proprietary data rights, nonexistence of technical data, etc.

A

Demilitarization Code (DEMIL_CD_0167)


Non-MLI/ Non-SLI — Demilitarization not required.

P

Hazardous Material Indicator Code (HMIC_0865)


Indicates there is no information in the HMIRS; however, the NSN is in a FSC in Table II of Federal Standard 313 and a MSDS may be required by the user. The requirement for a MSDS is dependent on a hazard determination of the supplier or the intended end use of the product.

A

Electrostatic Discharge Code (ESD_EMI_CD_2043)


No known Electrostatic Discharge (ESD) or Electromagnetic Interference (EMI) sensitivity.

A

Precious Metals Indicator Code (PMIC_0802)


Item does not contain Precious Metal.

0

ADPE Identification Code (ADPEC_0801)


Represents items with no ADP components. NOTE: Codes 1 through 6 are only to be used when the item is Automatic Data Processing Equipment (ADPE) in its entirety and is limited to the type meeting only one of the definitions for codes 1 through 6. (See code 9)


FLIS - SEG B - MOE RULE DATA | NSN 5925-01-483-0111 Submit RFQ
MOE RuleFormer MOEAMCAMSCNIMSCIMCIMC ActivityAACDSORCollaboratorsReceiversEffective Date
ZG011 Jan 2015
Code Definitions

FLIS - SEG C - REFERENCE NUMBER | NSN 5925-01-483-0111 Submit RFQ
RNFCRNCCRNVCDACRNAACRNSCRNJCSADCMSDSHCCReference NumberCAGE
43249ZDIEG6-1REC4-61-15.0-21-V  81541   CAGE/81541
Code Definitions

4

Reference Number Format Code (RNFC_2920)


Number is totally in-the-clear (without modification) as originally configured by the manufacturer, design control activity, or supplier.

3

Reference Number Category Code (RNCC_2910)


Design Control Reference. The primary number used to identify an item of production or a range of items of production, by the manufacturer (individual, company, firm, corporation, or Government activity) which controls the design, characteristics, and production of the item by means of its engineering drawings, specifications and inspection requirements.

2

Reference Number Variation Code (RNVC_4780)


A design control or other reference number that is an item-identifying number for an item of production, or a source control reference or a specification or standard part, type, or similar reference number that is an item-identifying number for an item of supply.

4

Document Availability Code (DAC_2640)


The reference number is represented by technical documentation other than a drawing and the documentation was available to the RNAAC, who may or may not be the submitting activity, at the time of submission of the reference number; however, the RNAAC cannot furnish the technical documentation.

9Z

Reference Number Action Activity Code (RNAAC_2900)


DLIS-K, Battle Creek, MI 49037-3084

D

Reference Number Status Code (RNSC_2923)


Procurement authority of the manufacturer and reference number have not yet been checked. NOTE: This code is to be allocated to reference numbers still requiring checks on procurement authority.


FLIS - SEG E - ITEM STANDARDIZATION DATA | NSN 5925-01-483-0111 Submit RFQ
ISCOriginatorNIIN StatusReplaced / Replacement ISCReplaced / Replacement OriginatorReplacement NIIN StatusReplacement DateReplaced / Replacement NSNDecision Date
597613 Mar 2001
Code Definitions

5

Item Standardization Code (ISC_2650)


An item authorized for procurement that has not yet been subject to item standardization.

97

Originator of Standardization Decision (ORG_STDZN_DEC_9325)


DLIS-LFF, Battle Creek, MI 49037-3084

6

NIIN Status Code (NIIN_STAT_CD_2670)


Item is inactive (no recorded Primary/Secondary Inventory Control Activity (PICA/SICA)). File data coded KFD is forwarded.

13 Mar 2001

Standardization Decision Date (DT_STDZN_DEC_2300)


FLIS - SEG G - FREIGHT DATA | NSN 5925-01-483-0111 Submit RFQ
IntegrityOriginatingHMCLCLWCCTCCSHCADCACCASHLTLNMFCNMFC Sub ItemUFCFreight DescriptionRail Variance
Code Definitions

DX

Originating Activity Code (ORIG_ACTY_CD_4210)


Rail Variance

Rail Variance (RAIL_VARI_CD_4760)


No Variation. NMFC and UFCC Match.


FLIS - SEG M/V - CHARACTERISTICS DATA | NSN 5925-01-483-0111 Submit RFQ
MRCDecoded RequirementClear Text Reply
CPRZAuxiliary Switch Function And Quantity1 CONTROL
CPRKAuxiliary Trip Coil Voltage Type And Rating In Volts125.0 AC NOMINAL ALL LOCATIONS
ADAQBody Length2.000 INCHES NOMINAL
ADATBody Width0.750 INCHES NOMINAL
AEBPCenter To Center Distance Between Terminals Parallel To Length1.530 INCHES NOMINAL
CPRHCircuit Protection TypeOVERCURRENT ALL LOCATIONS
FREQFrequency In Hertz50.0 ALL LOCATIONS OR 60.0 ALL LOCATIONS
CPRGMaximum Interrupting Capacity Current Type And Rating Per Pole In Amps2000.0 AC ALL LOCATIONS
CPLMMaximum Continuous Load Current Rating Per Pole15.0 AMPERES AC ALL LOCATIONS
CPRFOperating Voltage Type And Rating Per Pole In Volts250.0 AC ALL LOCATIONS
CQXFInclosure Protection Type For Which DesignedCORROSION RESISTANT AND MOISTURE RESISTANT AND SALT WATER RESISTANT AND SHOCK RESISTANT AND VIBRATION RESISTANT
CPSMInternal Trip Release ConfigurationSERIES/RELAY TRIP ALL LOCATIONS
CPRRMain Contact Tripping Mechanism TypeTRIP FREE
AKPXPole Quantity1
CPRQReset MethodMANUAL
FEATSpecial FeaturesVDE APPROVED; TOGGLE HANDLE COLOR IS RED - MARKED WITH WHITE LETTERS OF ON/OFF AND I/O; APROXIMATE WEIGHT PER POLE 2.2 OUNCES; DIELECTRIC STRENGTH WITH AUXILIARY SWITCHED TERMINALS 600 VOLTS AC, 60 HERTZ
CPRLTrip Release CharacteristicTIME DELAY ALL LOCATIONS
CQQCTrip Release Duty CycleCONTINUOUS ALL LOCATIONS
CPRJTrip Release MethodMAGNETIC-HYDRAULIC ALL LOCATIONS
CQWNTrip Delay Time In Seconds Per Rated Continuous Current0.700 MINIMUM AT 125 PCT ALL LOCATIONS AND 12.000 MAXIMUM AT 125 PCT ALL LOCATIONS AND 0.350 MINIMUM AT 150 PCT ALL LOCATIONS AND 7.000 MAXIMUM AT 150 PCT ALL LOCATIONS AND 0.130 MINIMUM AT 200 PCT ALL LOCATIONS AND 3.000 MAXIMUM AT 200 PCT ALL LOCATIONS AND 0.030 MINIMUM AT 400 PCT ALL LOCATIONS AND 1.000 MAXIMUM AT 400 PCT ALL LOCATIONS AND 0.015 MINIMUM AT 600 PCT ALL LOCATIONS AND 0.300 MAXIMUM AT 600 PCT ALL LOCATIONS AND 0.010 MINIMUM AT 800 PCT ALL LOCATIONS AND 0.150 MAXIMUM AT 800 PCT ALL LOCATIONS AND 0.008 MINIMUM AT 1000 PCT ALL LOCATIONS AND 0.100 MAXIMUM AT 1000 PCT ALL LOCATIONS
CPRNUltimate Trip Rating Of Continuous Current Rating Per Pole In Percent125.0 ALL LOCATIONS
CPRPUltimate Trip Time Per Pole In Seconds0.700 MINIMUM ALL LOCATIONS AND 12.000 MAXIMUM ALL LOCATIONS
AAQLBody Style
AEGJSwitch Contact ArrangementSINGLE POLE, DOUBLE THROW
CSSXSwitch Current Rating And Type In Amps1.0 AC
CQSMSwitch Location And Position DesignationINTERNAL AT POLE ONE
CRTKSwitch Terminal TypeQUICK DISCONNECT, MALE
CSWPSwitch Voltage Rating And Type In Volts125.0 AC
TTQYTerminal Type And Quantity2 SCREW