5925-01-583-6372

CIRCUIT BREAKER


5925-01-583-6372 (5925015836372, 015836372)
Part Number (1 listing): AP-12-1-7-1-702
Summary

FSG 59 / FSC 5925

DEMIL: A

DEMIL INT: 1

HMIC: P

Date Created: 31 Mar 2010

MSDS: None

Hazmat: None

Request a Quote


;



MASTER CROSS REFERENCE LIST (MCRL) | NSN 5925-01-583-6372 Submit RFQ
Manufacturer Part NumberRNCCRNVCManufacturer NameCAGE
AP-12-1-7-1-7022 - Definitive Specification or Standard Document2 - Production ItemMILITARY SPECIFICATIONS  81349    CAGE 81349  
Code Definitions

2 - Definitive Specification or Standard Document

Reference Number Category Code (DRN_2910)


Definitive Government Specification or Standard Designator Reference. A part number, style number, or type designator included in or developed in accordance with a Government specification or standard which has the effect of fully identifying an item of supply. This code shall also be used for a Government specification or standard which, although not including part numbers, style numbers, or type designators, covers a single item of upply. These reference numbers may be coded with Reference Number Variation Code (RNVC) 1 in accordance with volume 2, paragraph 2.9.2.n.(4).

2 - Production Item

Reference Number Variation Code (DRN_4780)


A design control or other reference number that is an item-identifying number for an item of production, or a source control reference or a specification or standard part, type, or similar reference number that is an item-identifying number for an item of supply.


FLIS - SEG A - IDENTIFICATION | NSN 5925-01-583-6372 Submit RFQ
FSGFSCNIINFIIGINCCRITICALITYTYPE OF ITEMMRCDEMILHMICEDCPMICADPECDATE CREATED
595925015836372A030A000136X1APAA031 Mar 2010
Code Definitions

59

Federal Supply Group (FSG_3994/FSC_WI_FSG_3996)


Electrical and Electronic Equipment Components

5925

Federal Supply Class (FSC_3994/FSC_WI_FSC_3996)


Circuit Breakers

015836372

National Item Identification Number (NCB_CD_4130/I_I_NBR_4131)


NSN 5925-01-583-6372

A030A0

Federal Item Identification Guide (FIIG_4065)

00136

Item Naming Code (INC_4080)

31 Mar 2010

NIIN Assignment Date (DT_NIIN_ASGMT_2180)

X

Item Criticality (CRITL_CD_FIIG_3843)


The item does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application.

1

Type of Item Identification (TYP_II_4820)


Full Descriptive Item Identification

A

Demilitarization Code (DEMIL_CD_0167)


Non-MLI/ Non-SLI — Demilitarization not required.

P

Hazardous Material Indicator Code (HMIC_0865)


Indicates there is no information in the HMIRS; however, the NSN is in a FSC in Table II of Federal Standard 313 and a MSDS may be required by the user. The requirement for a MSDS is dependent on a hazard determination of the supplier or the intended end use of the product.

A

Electrostatic Discharge Code (ESD_EMI_CD_2043)


No known Electrostatic Discharge (ESD) or Electromagnetic Interference (EMI) sensitivity.

A

Precious Metals Indicator Code (PMIC_0802)


Item does not contain Precious Metal.

0

ADPE Identification Code (ADPEC_0801)


Represents items with no ADP components. NOTE: Codes 1 through 6 are only to be used when the item is Automatic Data Processing Equipment (ADPE) in its entirety and is limited to the type meeting only one of the definitions for codes 1 through 6. (See code 9)


FLIS - SEG B - MOE RULE DATA | NSN 5925-01-583-6372 Submit RFQ
MOE RuleFormer MOEAMCAMSCNIMSCIMCIMC ActivityAACDSORCollaboratorsReceiversEffective Date
ZH011 Jun 2011
Code Definitions

FLIS - SEG C - REFERENCE NUMBER | NSN 5925-01-583-6372 Submit RFQ
RNFCRNCCRNVCDACRNAACRNSCRNJCSADCMSDSHCCReference NumberCAGE
422E9ZDAP-12-1-7-1-702  81349   CAGE/81349
Code Definitions

4

Reference Number Format Code (RNFC_2920)


Number is totally in-the-clear (without modification) as originally configured by the manufacturer, design control activity, or supplier.

2

Reference Number Category Code (RNCC_2910)


Definitive Government Specification or Standard Designator Reference. A part number, style number, or type designator included in or developed in accordance with a Government specification or standard which has the effect of fully identifying an item of supply. This code shall also be used for a Government specification or standard which, although not including part numbers, style numbers, or type designators, covers a single item of upply. These reference numbers may be coded with Reference Number Variation Code (RNVC) 1 in accordance with volume 2, paragraph 2.9.2.n.(4).

2

Reference Number Variation Code (RNVC_4780)


A design control or other reference number that is an item-identifying number for an item of production, or a source control reference or a specification or standard part, type, or similar reference number that is an item-identifying number for an item of supply.

E

Document Availability Code (DAC_2640)


The reference number is represented by engineering data other than an engineering drawing. The data is available for unlimited use and will be furnished by the activity identified by the RNAAC upon request.

9Z

Reference Number Action Activity Code (RNAAC_2900)


DLIS-K, Battle Creek, MI 49037-3084

D

Reference Number Status Code (RNSC_2923)


Procurement authority of the manufacturer and reference number have not yet been checked. NOTE: This code is to be allocated to reference numbers still requiring checks on procurement authority.


FLIS - SEG E - ITEM STANDARDIZATION DATA | NSN 5925-01-583-6372 Submit RFQ
ISCOriginatorNIIN StatusReplaced / Replacement ISCReplaced / Replacement OriginatorReplacement NIIN StatusReplacement DateReplaced / Replacement NSNDecision Date
597031 Mar 2010
Code Definitions

5

Item Standardization Code (ISC_2650)


An item authorized for procurement that has not yet been subject to item standardization.

97

Originator of Standardization Decision (ORG_STDZN_DEC_9325)


DLIS-LFF, Battle Creek, MI 49037-3084

0

NIIN Status Code (NIIN_STAT_CD_2670)


Item is active. File data coded KFD is forwarded. if this KFD data represents your item of supply, submit, if applicable, an LAD, LAU, or LCU transaction. Otherwise, use the National Stock Number (NSN) in your supply system.

31 Mar 2010

Standardization Decision Date (DT_STDZN_DEC_2300)


FLIS - SEG G - FREIGHT DATA | NSN 5925-01-583-6372 Submit RFQ
IntegrityOriginatingHMCLCLWCCTCCSHCADCACCASHLTLNMFCNMFC Sub ItemUFCFreight DescriptionRail Variance
ZH
Code Definitions

ZH

Originating Activity Code (ORIG_ACTY_CD_4210)


Republic of Korea

Rail Variance

Rail Variance (RAIL_VARI_CD_4760)


No Variation. NMFC and UFCC Match.


FLIS - SEG M/V - CHARACTERISTICS DATA | NSN 5925-01-583-6372 Submit RFQ
MRCDecoded RequirementClear Text Reply
CPRWActuator FunctionTRIP-RESET
CPRXActuator Position DesignationBETWEEN POLE ONE AND TWO
ADAQBody Length1.531 INCHES MINIMUM AND 1.562 INCHES MAXIMUM
AAQLBody StyleMULTIPOLE-SINGLE ACTUATOR TYPE
ADATBody Width1.250 INCHES MINIMUM AND 1.281 INCHES MAXIMUM
ABXDBushing Length0.332 INCHES MINIMUM AND 0.380 INCHES MAXIMUM
ADTVCase MaterialMETAL
AEBQCenter To Center Distance Between Terminals Parallel To Width0.594 INCHES MINIMUM AND 0.906 INCHES MAXIMUM
AEBPCenter To Center Distance Between Terminals Parallel To Length0.875 INCHES MINIMUM AND 0.906 INCHES MAXIMUM
CPRHCircuit Protection TypeOVERCURRENT ALL LOCATIONS
FREQFrequency In Hertz400.0 ALL LOCATIONS
CPLMMaximum Continuous Load Current Rating Per Pole5.0 AMPERES AC ALL LOCATIONS AND 5.0 AMPERES DC ALL LOCATIONS
CPRGMaximum Interrupting Capacity Current Type And Rating Per Pole In Amps300.0 AC ALL LOCATIONS AND 500.0 DC ALL LOCATIONS
AXHRMounting Facility Type And Quantity1 THREADED BUSHING W/PANEL SEAL
AJWXMounting Surface To Terminal End Distance1.797 INCHES MINIMUM AND 1.828 INCHES MAXIMUM
CQJXNominal Thread Size0.375 INCHES
CPRFOperating Voltage Type And Rating Per Pole In Volts240.0 AC ALL LOCATIONS AND 50.0 DC ALL LOCATIONS
CPSMInternal Trip Release ConfigurationSERIES TRIP ALL LOCATIONS
CPRRMain Contact Tripping Mechanism TypeTRIP FREE
CPRTManual Actuator Type And Quantity1 TOGGLE
AKPXPole Quantity2
CPRQReset MethodMANUAL
AAJEThread Pitch Diameters+0.3503/+0.3537 INCHES
THSDThread Series DesignatorUNEF
CMLPThread Quantity Per Inch32
CQWNTrip Delay Time In Seconds Per Rated Continuous Current0.500 MINIMUM AT 200 PCT ALL LOCATIONS AND 0.900 MAXIMUM AT 200 PCT ALL LOCATIONS
CPRLTrip Release CharacteristicTIME DELAY ALL LOCATIONS
CPRJTrip Release MethodMAGNETIC ALL LOCATIONS
CPRNUltimate Trip Rating Of Continuous Current Rating Per Pole In Percent125.0 ALL LOCATIONS
TTQYTerminal Type And Quantity4 WIRE HOOK


Back to Top