AC HEATER/EVAPORATOR BLOWER OPERATES BUT NO COLD AIR FROM
DUCTS DURING AC OPERATIONS - Continued
DRAFT
END OF WORK PACKAGE
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
- -
-
-
-
-
-
-
-
-
-
-
Step 7.
Open driver side engine cover and remove engine side panel
(TM 9-2320-279-10).
HEMAC128
Step 8.
Inspect AC compressor belts for looseness and damage.
If AC compressor belts are loose, damaged, or missing, notify Field
Level Maintenance.
Step 9.
Install engine side panel and close driver side engine cover
(TM 9-2320-279-10).
Step 10.
Start engine and operate AC system (WP 0004).
If AC system fails to provide cold air, or stops providing cold air during
normal operations, notify Field Level Maintenance.
Table 3-2. Operator’s Troubleshooting (Continued)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
WP
SEQUENCE
NO.