TM 9-2320- 209-20-2-1
From step 6
‘
●
Clean and test circuit breaker for
continuity
●
Take off externa I power source
to van. Refer to
TM 9-2320-209-10
●
Clean front and rear terminals
of circuit breaker. Refer to
Vol 3, chapter 18, para 18-70
●
Set mu Itimeter to measure
continuity.
Refer to test
equipment procedures index
●
Set circuit breaker to ON
●
●
●
Put multimeter + lead on front
terminal of circuit breaker
Put multimeter - lead on rear
terminal of circuit breaker
Read mu I timeter. Multi meter
should measure zero ohms
Does mu ltimeter measure zero ohms?
m
REAR
TERMINAL
CIRCUIT
BREAKER
T
FRONT
TERMINAL
—
GO
Figure 25-42 (Sheet 5 of 6)
TA 114525
25-319