TM 9-2320-365-10
Change 2
3-66.1/(3-66.2 Blank)
Table 3-2.
Troubleshooting (Cont)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
e107.
M1079 110 VAC OUTLET J231 DOES NOT OPERATE (CONT).
(b)
If circuit breaker is tripped, position to ON to reset.
(c)
Check to see if 110 vac outlet J231 operates.
(d)
If 110 vac outlet J231 does not operate, or circuit breaker trips again, notify Unit
Maintenance.
e108.
M1079 110 VAC OUTLET J230 DOES NOT OPERATE.
Check circuit breaker (CB9) in 110/208 VAC POWER DISTRIBUTION PANEL to see if it is tripped.
(a)
Open 110/208 VAC POWER DISTRIBUTION PANEL cover (para 2-32).
(b)
If circuit breaker is tripped, position to ON to reset.
(c)
Check to see if 110 vac outlet J230 operates.
(d)
If 110 vac outlet J230 does not operate, or circuit breaker trips again, notify Unit
Maintenance.
e109.
M1079 BLACKOUT LIGHT(S) DOES NOT ILLUMINATE.
Step 1.
Check circuit breakers (CB10 and CB11) on relay box to see if either is tripped.
(a)
If circuit breakers (CB10 or CB11) are tripped, push in to reset.
(b)
Check to see if blackout lights operate.
(c)
Circuit breakers (CB10 or CB11) trips again, notify Unit Maintenance.
Step 2.Check to see if emergency lights illuminate (para 2-34).
If emergency lights do not illuminate, perform Electrical System Troubleshooting para e114.
M1079
24 VDC Binding Post(s) Does Not Operate.
If emergency lights do illuminate, notify Unit Maintenance.
e110.
ONE OR MORE M1079 EMERGENCY LIGHTS DO NOT ILLUMINATE.
Step 1.
Check circuit breakers (CB10 and CB11) on relay box to see if either is tripped.
(a)
If circuit breakers (CB10 or CB11) are tripped, push in to reset.
(b)
Check to see if emergency lights operate.
(c)
Circuit breakers (CB10 or CB11)
trip again, notify Unit Maintenance.
Step 2.
Check to see if blackout lights illuminate (para 2-34).
If blackout lights do not illuminate, perform Electrical System troubleshooting para e114.
M1079 24
VDC Binding Post(s) Does Not Operate.
If blackout lights illuminate, notify Unit Maintenance.