46
PS 688
MAR 10
PS 688
Change the words under the
FUNCTION heading in Table
10, Key 1 for the MEP-809 and
Key 6 for the MEP-807, GND
Jumper, to read: “
Jumper bonds
the Neutral to ground. This bar
shall NOT be removed unless
the system level equipment
being
powered
requires
an
ungrounded system.”
Now change or add the
following
WARNING
above
Table 10, Output Load Board
Terminal TB2 Connections in
the MEP-807 and -809 TMs
and at the beginning of the
“Assembly and Preparation for
Use, Installation of Load Cables”
section of the 5-, 60-kW TQG’s
TMs.
WARNING
“Do
not
remove the Bonding Jumper
between GND and N unless
the weapon system requires an
ungrounded system. Failure
to comply can cause death
or serious injury. Refer to
applicable
Weapon
System
TM
for
speci±c
guidance
on
power
and
connection
requirements.”
These changes need to be made
immediately. And
inform
all
operators and maintainers of the
TQGs, immediately.
When the TMs are updated, the
pages with the new information
will be added.
In the meantime, you
must
make
these
corrections
on
whatever page addresses the
output load terminal board TB2
showing the ground bar jumper.
NSN
5995-01-
Length
(feet)
2
3
4
5
6
8
11
13
14
18
19
21
50
100
302-0059
219-7010
219-4703
300-9291
219-4704
259-9283
225-1657
259-9282
219-4705
219-4706
303-4950
219-1844
358-1078
382-6869
Neutral
to Ground
Bar Safety
Issue
±²³to³´µµ²kW³TQG…
Neutral
to Ground
Bar Safety
Issue
SINCGARS…
Cabling
the
LS-671
warning!
iF YOUR UNiT HAS
MOBiLE ELECTRiC POWER (MEP) 5-,
10-, 15-, 30-, 60-, 100- OR 200-kW
TQGs,
MODELS MEP-802/812,
-803/813, -804/814A OR B,
-805/815A OR B, -806/816A OR
B, -80
7
OR -809…
specifically, you
needed to
amend
the information
about the
output
load terminal
bOard TB2.
the special purpose cable,
cx-13292/vrc, that connects
the ls-6
7
1/vrc loudspeaker
to the SINCGARS radio,
comes in many lengths.
an added benefit to these multiple
lengths is the flexibility it gives you to
take the pressure off a taut cable.
an 8-ft cable
can bring
relief
to a 6-ft
cable that is
stretched to
its limit.
here’s a list of
the available
lengths for the
cx-13292/vrc
special purpose
cable…
these lengths allow the loudspeaker
to be installed in different
configurations to meet the needs of
different types of vehicles.
…YOU NEED TO ADD AN iMPORTANT
WARNiNG TO THE
“DESCRiPTiON AND
USE OF OPERATOR CONTROLS AND
iNDiCATORS”
OR THE
“ASSEMBLY
AND PREPARATiON FOR USE,
iNSTALLATiON OF LOAD CABLES”
SECTiONS OF THE TM.
if you have
an MEP-80
7
,
TM 9-6115-
7
29-10,
the information
you need to modify
is in WP 0005 00-1
7
.
688.46-47.indd
1-2
2/5/10
10:23:22 AM
Click here for a copy of these articles to save or email.