Table 4-1.
Unit Preventive Maintenance Checks and Services for Model HTARS100.
Item
Location
No.
Interval
Item
Procedure
Check/Service
1
Monthly
All Fuel Hoses
Using a multimeter, test fuel hose for broken, or disconnected
internal ground cable as follows:
(1)
Place multimeter leads against metal surfaces of both
couplings.
(2)
Check for continuity between couplings.
Continuity must
exist.
If continuity does not exist, hose is defective.
4-5/(4-6 Blank)