TM 5-4210-249-13&P-1
0027-1
DRAFT
0027
OPERATOR MAINTENANCE
PUMPING FROM HYDRANT OR IN RELAY (POSITIVE WATER SOURCES)
NOTE
•
Make sure valves, drains, and caps are closed.
•
Foam system will not operate when pump intake pressure is more than 5 psi (34 kPa).
•
Main Inlet may be operated with either 5 in. (13cm) or 3 in. (7.6 cm) suction hose.
•
5 in. (13 cm) and 3 in. (7.6 cm) suction hoses operate the same way.
5 in. (13 cm) suction
hose shown.
1.
Position vehicle for convenient hydrant hookup and discharge hose layout.
Bring vehicle to complete stop.
2.
Park vehicle (TM 9-2320-347-10).
NOTE
Pumping may be performed from either main inlet or PASSENGER SIDE AUX. INLET.
3.
Remove cap from either main inlet (1) or PASSENGER SIDE AUX. INLET (2).
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Do not use hard suction hose for Step (4).
Hard suction hose will not hold pressure.
Hose may fail and separate causing injury to personnel and/or damage to
equipment.
4.
Connect either 5 in. (13 cm) soft suction hose to main inlet (1) or 3 in. (8 cm) discharge hose to PASSENGER
SIDE AUX. INLET (2).
TFFT00321P/00322P
WARNING
ICON 72