TM 5-4210-249-13&P-1
0034-2
DRAFT
0034
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
4.
Put FOAM SELECT switch (5) to desired foam agent.
Indicator light A (6) or light B (7) will illuminate.
5.
Make sure correct foam indicator light A (6) or light B (7) is illuminated.
6.
Establish water flow to desired discharge outlet(s) (WP 0028).
NOTE
•
Foam system agent percentage is preset for turrets and ground sweeps and is not
adjustable.
•
The foam system will discharge class A foam at 0.5% at 200 to 210 psi (1,379 to
1,448 kPa).
At pressures lower than 200 psi (1,379 kPa), the foam concentrate will be
higher.
7.
For class A foam, use pressure governor to adjust discharge pressure to desired pressure (WP 0024),
depending on type of operation.
NOTE
•
The foam system will discharge class B foam at 3% at 200 to 210 psi (1,379 to 1,448 kPa).
Class B foam should not be discharged at reduced pressures.
•
Activating the PRESET switch on the pressure governor (pressure mode), will
automatically increase the discharge pressure to 200 to 210 psi (1,379 to 1,448 kPa).
8.
For class B foam, use pressure governor to adjust discharge pressure to 200 to 210 psi (1,379 to 1,448 kPa)
(WP 0024).
END OF TASK
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-