TM 5-4210-249-13&P-1
0077-2
DRAFT
0077
TFFT04404
NOTE
The message center must display MODE on pump operator’s panel governor control
panel, before entering the password.
Message center will display xxx3-5xx after entering
self-test password.
Step 4.
Perform pressure governor self-test on pump operator’s panel pressure governor by
entering self-test password IDLE INC IDLE INC IDLE INC IDLE INC.
Press each key
on pressure governor, watch message display for a letter indicating which switch is
being pressed.
Once all switches, on pump operator’s panel pressure governor are
pressed, a “2“ will be displayed in position 2.
If a letter is displayed constantly, letter is not displayed when pressed, or “2”
is not displayed in position 2, replace pump operator’s panel pressure
governor panel (WP 0332).
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION