TM 5-4210-249-13&P-1
0099-7
DRAFT
0099
CAUTION
•
Do not mix different types or brands of foam agent in foam cells or piping.
Mixing
of different foam agents (either type or manufacturer) may cause deterioration of
foam agent, improper proportioning and poor performance in a fire situation.
Mixing of Class A and Class B foam agents may result in a chemical
reaction which
can create globules, which can clog orifices and cause system failure.
•
Failure to flush foam system after each foam use could result in equipment damage.
NOTE
•
Do not open foam agent supply tanks while performing flush procedures.
•
Before flushing system make sure that FOAM SYSTEM switch is in off
position (WP 0004).
Step 7.
Start water pump engine (WP 0022).
Put pump operator’s panel FOAM FLUSH switch
to ON position (WP 0004).
Flush foam system (WP 0031).
Put pump operator’s panel
FOAM FLUSH switch to OFF position (WP 0004).
Put cab FOAM SYSTEM switch to
on position (WP 0004).
Put FOAM SELECT switch to “A” position (WP 0004).
Put
TANK TO PUMP switch to ON position (WP 0004).
Put GROUND SWEEPS switch to
on position (WP 0004).
Flush foam system (WP 0031).
Retest system with foam B
selected.
Check if foam is delivered from under truck nozzles in either foam A or foam
B.
a.
If foam is delivered from ground sweeps, fault corrected.
b.
If foam is not delivered from ground sweeps, replace foam system
multi-metering valve (WP 0292).
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION