TM 5-3895-372-20
WATER SYSTEM.
5-11. SIGHT GAGE MAINTENANCE (Continued).
LOCATION/ITEM
ACTION
REMARKS
A.
REMOVAL.
1.
Gage valve (4).
Turn handle clockwise to close.
2.
Draincock (5).
Open and drain gage tube (1).
3.
Gage collar nut (3).
Unscrew from gage valve ({4).
4.
Gage tube (1).
Remove from gage valve (4).
Remove by lifting up through
three gage tube brackets (6).
5.
Three grommets (2).
Remove from three gage tube
Replace if deteriorated.
brackets (6).