FIXED FIRE EXTINGUISHER CONTROL VALVE REPLACEMENT (Sheet 11 of 14)
20.
Using adjustable wrench, install plug
(U) in housing (V).
21.
Push cable (W) through plug (U) and
around sheave (X).
22.
Lay cable (W) in retainer (Y).
23.
Extend cable (W) full length of retainer
(Y) and no further.
24.
Coat threads of two screws (Z) with sealant.
25.
Using 3/32 inch allen wrench, install two screws (Z) securing cable (W) in retainer (Y).
26.
Place sheave (X), cable (W), and retainer (Y) in housing (V) in approximately the position
shown. Cable end of retainer (Y) must be against pin on sheave (X).
27.
Using spring scale, pull against cable (W) with about 150 pounds of force to make sure
cable (W) is secured by screws (Z).