REPAIR RADIATOR — Continued
0025 00
3.
Flush radiator until water from radiator inlet opening (6) runs clear.
TEST RADIATOR FOR FLOW
1.
Plug auxiliary tank connection opening (4). Use radiator test plug set.
2.
Using radiator flow test machine, connect supply hose to radiator inlet (6).
3.
Connect return hose of test machine to radiator outlet (5).
4.
Flow test radiator at 70-80 gallons (276-292 liters) per minute. See TM 750-254.
5.
If pressure drop is more than 4 p si (28 k Pa), disassemble radiator and rod o ut radiator core. S ee R
ODDING