TM 9-2920-257-30&P
16.
Add incremental loads up to 200 amps.
Voltage should remain constant.
17.
If 28 volts cannot be sustained at various settings, regulator is defective.
18.
Reduce loads one at a time, until load is zero at completion of test.
19.
Reduce test stand speed to 1000 RPM.
20.
Press STOP button.
Wait for test stand to come to a complete stop.
21.
Return test stand switches and controls to base settings (para E-3).
22.
Remove generator and regulator from test stand.
Figure E-1.
200 AMP Generator Performance Curves
Change 1
E-7/(E-8 Blank)