TM-5-4210-249-13-P-2

TACTICAL FIRE FIGHTING TRUCK (TFF) MODEL M1142

TECHNICAL MANUAL; OPERATOR’S AND FIELD LEVEL MAINTENANCE MANUAL WITH REPAIR PARTS AND SPECIAL TOOLS LIST (INCLUDING DEPOT REPAIR PARTS AND SPECIAL TOOLS); PART 2 OF 4

  TM-5-4210-249-13-P-2 - Page 530 of 1452

TM 5-4210-249-13&P-2
0165-6
DRAFT
0165
TFFT03919
Step 9.
Check continuity across circuit breaker 2.
If there is no continuity, replace circuit breaker (WP 0360).
Step 10.
Check continuity across circuit breaker 4.
If there is no continuity, replace circuit breaker (WP 0360).
Step 11.
Check cord reel receptacles for proper operation (WP 0037).
a.
If receptacle(s) do not operate, replace cord reel receptacle box
(WP 0377).
b.
If circuit breakers 2 or 4 trip when a receptacle is being used, switch
item being powered.
c.
If circuit breakers 2 or 4 continue to trip, replace circuit breaker that is
tripping (WP 0360).
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION