TM 9-2320-328-13&P-1
0061-4
DRAFT
0061
HWT0511
Step 4.
Put FOAM FLUSH switch to OFF position (WP 0004).
Inspect foam flush valve tubing
between foam flush valve and foam metering manifold for kinks and damage.
a.
If foam flush valve tubing is free from kinks and/or damage, clean or
replace foam flush strainer screen (WP 0183).
b.
If foam flush valve tubing is kinked or damaged, replace damaged
tubing (WP 0320).
Step 5.
Put FOAM FLUSH switch to OFF position (WP 0004).
While an assistant puts cab or
pump operator’s panel FOAM SYSTEM switch to ON position (WP 0004), check if
eductor valve operates to open position.
If eductor valve does not operate to open position, go to Step 8.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION