TM-10-5411-205-13

SHELTER, ELECTRICAL EQUIPMENT - 250/G

TECHNICAL MANUAL; OPERATOR’S, UNIT, AND DIRECT SUPPORT MAINTENANCE MANUAL

MAY 1995
CHANGE 2

  TM-10-5411-205-13 - Page 15 of 127

TM 10-5411-205-13
2-3.
Explanation of columns (cont).
d .
Equipment is Not Ready/Available If.
This column tells you when and why your
equipment cannot be used.
Item
1
2
3
4
NOTE
Perform your “weekly checks” in addition to the “before checks” if
you are the assigned operator and have not operated the equipment
since the last weekly check was performed, or if you are operating
the equipment for the frost time.
Table 2-1. Operator Preventive Maintenance Checks and Services.
NOTE
Within designated interval, these checks are to be performed in the
order listed.
Item to be
Inspected
Door Handles
Louver Cover
Assembly (Inner
Door)
Door Stay
Assemblies
Door Assemblies,
Inner and Outer
Procedures
Check for and have repaired
or adjusted as necessary
Make sure handles on inner
and outer doors operate smooth
ly without binding or jamming.
a. Make sure louver cover
assembly can be held in the
open position.
b. Make sure weather gasket
is in good condition.
c. Make sure air filter,
louvers and directional vanes
are not blocked.
Make sure that each door stay
assembly rod slides smoothly in
channel and rotates easily in
bracket. Check for loose or
missing hardware or detent pin
a. Make sure doors open and
close smoothly without binding
Check hinges for loose loose
or missing hardware. Lubri-
cate hinges.
b. Make sure rain flap above
louver cover assembly is intact.
Item is
Not Ready/
Available if
Door cannot be
opened or cannot
be closed securely.
a. Louver cover
assembly cannot be
held open.
c. Air filters,
louvers or vanes are
blocked.
a. Door cannot be
opened or cannot
be closed securely.
2-2