HWT0354
.
WARNING
.
ICON 26,66
.
Be sure to wear proper eye protection to prevent injury or death.
If air lines are
under pressure when they are disconnected, they can whip around and cause
injury to personnel.
Caution should be exercised when disconnecting air line
fittings.
Be sure to wear proper eye protection to prevent injury or death.
Air lines may be
under pressure when control valve is operated.
If under pressure and air lines are
disconnected, air lines may whip around and cause injury to personnel.
Caution
should be exercised when operating control valve with air lines disconnected.
.
NOTE
Air pressure is checked by disconnecting air line at eductor valve and observing air
pressure escaping from air line, when eductor control valve is activated.
Air will escape
from the blue air line when FOAM SYSTEM switch is positioned to the ON position.
System air pressure may drop below 85 psi (586 kPa) during this procedure.
.
Step 21.
Disconnect air line at eductor valve.
While an assistant puts cab or pump operator’s
panel FOAM SYSTEM switch to on position (WP 0004), check if air pressure is present
at eductor valve.
.
If there is air pressure, replace eductor valve (WP 0178).
.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION