TM-9-2350-277-20-2

CARRIER M113A3, M577A3, M1059A3, M1064A3, M1068A3 AND M58

TECHNICAL MANUAL; UNIT MAINTENANCE MANUAL VOLUME 2 OF 6

  TM-9-2350-277-20-2 - Page 125 of 783

TM 9-2350-277-20-2
PREVENTIVE MAINTENANCE CHECKS AND SERVICES (PMCS), INCLUDING
LUBRICATION INSTRUCTIONS — Continued
0155 00
ITEM
NO.
INTERVAL
MAN-
HOUR
ITEM TO BE
CHECKED OR
SERVICED
CREWMEMBER
PROCEDURE
EQUIPMENT
NOT READY/
AVAILABLE
IF:
69
Semi-
Annual
Fixed Fire
Extinguisher
0155 00-105
Change 5
CAUTION
Fire extinguisher control valve sealed
with steel wire will not work. Make
sure seal wire is made out of .020 light
copper.
a.
Remove and weigh fixed fire extinguisher
cylinder (WP 0898 00).
Extinguisher
is missing or
seal/lockwire
missing or
broken, bottles
are overdue
for hydrostatic
test. Lock wire
is not .020 light
copper.
b.
Recharge or exchange fire extinguisher
if weight loss is more than 10 percent of
charged weight stamped on bottle.
c.
Inspect fire extinguisher cylinder data
plate to ensure that a hydrostatic test has
been performed within the past 5 years.
Faulty extinguishers, or those beyond the
test time limit (5 years), shall be declared
unserviceable and replaced.
CAUTION
Fire extinguisher control valve sealed
with steel wire WILL NOT work. Use
.020 thin copper wire.
d.
Before reconnecting cylinder, operate
discharge handles to be sure cables and
controls work properly.
e.
Install cylinder and replace copper seal
wires (WP 0898 00).
f.
Replace discharge tubes that are crimped,
plugged, or cracked (WP 0899 00).


Back to Top