TM 9-2320-328-13&P-1
0071-19
DRAFT
0071
HWT0528
NOTE
•
Ensure system air pressure is at least 85 psi (586 kPa) during this procedure.
System air
pressure is required to activate valves.
•
Do not engage PUMP PTO during this procedure, except when performing complete
system checks.
Valve operations can be checked without water pump operation.
•
Valve operations can be checked by observing valve shaft rotation.
Step 27.
While an assistant puts cab PUMP COOLER switch to on position (WP 0004), check if
pump cooler valve operates to open position.
If pump cooler valve does not operate to open position, go to Step 34.
HWT1199
Step 28.
Put cab PUMP COOLER switch to off position (WP 0004).
Put pump operator’s panel
REEL DISCHARGE switch to ON position (WP 0004).
Check if REEL DISCHARGE
indicator illuminates.
If REEL DISCHARGE indicator does not illuminate, go to Step 32.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION