TM-9-2920-257-30-P

GENERATOR, ALTERNATING CURRENT, 200 AMPERES

TECHNICAL MANUAL; DIRECT SUPPORT MAINTENANCE MANUAL INCLUDING REPAIR PARTS AND SPECIAL TOOLS

MAY 1987

  TM-9-2920-257-30-P - Page 70 of 111

TM 9-2920-257-30&P
(23.) Install pulley bushing (6) on generator shaft.
(24.) Press woodruff key (5) into shaft.
(25.) Align pulley (3) with woodruff key (5) and install on generator shaft.
(26.) Install hardened washer (2) and pulley nut (1) on shaft.
NOTE
Support the generator and clamp the pulley in a vise with protective jaw caps.
Tighten the nut to 120 ft-lb torque.
(27.) Place fan assembly (9) on shaft from end housing 11).
(28.) With pulley (3) in vise, install washer (8) and nut (7) on generator shaft.
Tighten nut to 50 ft-lb torque.
Remove generator from vise.
d.
Generator Performance Test.
See Appendix E.
3-40
Change 1


Back to Top