TM-9-2920-257-30-P

GENERATOR, ALTERNATING CURRENT, 200 AMPERES

TECHNICAL MANUAL; DIRECT SUPPORT MAINTENANCE MANUAL INCLUDING REPAIR PARTS AND SPECIAL TOOLS

MAY 1987

  TM-9-2920-257-30-P - Page 11 of 111

TM 9-2920-257-30&P
Table 2-1.
Generator Troubleshooting - Continued
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
Figure 2-2.
Shorted Positive Rectifier Test.
Check for shorted positive rectifiers .
Connect
ohmmeter to each of the three positive rectifier
leads in accordance with figure 2-2.
If the ohmmeter reading is less than 100,000
ohms,
replace drive end housing assembly in
accordance with paragraph 3-3, and go to step 8.
2-4
Step 4.