TM 9-2920-257-30&P
Table 2-1.
Generator Troubleshooting - continued
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
Figure 2-5.
Open Negative Rectifier Test.
Step 7.
Check for open negative rectifiers.
Connect
ohntmeter to each of the three negative rectifier
leads in accordance with figure 2-5.
If the ohmmeter reading is more than 100 ohms,
replace drive end housing assembly in
accordance with paragraph 3-3, and go to step 8.
2-7