Table 2-1.
Generator Troubleshooting - Continued
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
Figure 2-8.
Open Printed Circuit Panel Assembly Diode Check.
Step 10.
Check for open diodes on printed circuit panel
assembly.
Connect ohmmeter to each of the three
long black leads according to figure 2-8.
If ohmmeter reading is higher than 100,000
ohms ,
replace printed circuit panel assembly in
accordance with paragraph 3-3 and go to step 13.
2-10