TM-9-2920-257-30-P

GENERATOR, ALTERNATING CURRENT, 200 AMPERES

TECHNICAL MANUAL; DIRECT SUPPORT MAINTENANCE MANUAL INCLUDING REPAIR PARTS AND SPECIAL TOOLS

MAY 1987

  TM-9-2920-257-30-P - Page 44 of 111

TM
9-2620-257-30&P
d.
Generator Repair Procedure.
Replace unserviceable parts as
required.
e.
Generator Assembly Procedure.
(1) Upon reassembly,
all parts disturbed during disassembly,
except brushes and brush holder,
must be coated with epoxy enamel (item
3, App B).
(2) Install inside seal to drive end housing assembly (fig. 3-1).
(a) Pack all rectifier leads down inside cavity in drive end
housing assembly (21).
Place housing in arbor press with rectifiers
facing up.
CAUTION
Bearing will not seat properly if seal is not placed correctly.
Place seal on seal bore with seal lips flaring up.
(b) Place inside seal (22) in position on seal bore with seal lips
flaring
up . See figure 3–8 for proper seal lip position.
(c) Place ball bearing tool (fig. F-1) on top of inside seal (22)
according to figure 3-9.
Press in seal flush with bottom of bearing bore.
3-1 4


Back to Top