TM 9-2320-328-13&P-1
0057-34
DRAFT
0057
Change 1
.
HWT0347
.
NOTE
Ensure system air pressure is at least 85 psi (586 kPa) during this procedure.
System air
pressure is required to activate valves.
Do not engage PUMP PTO during this procedure, except when performing complete
system checks.
Valve operations can be checked without water pump operation.
Valve operations can be checked by observing valve shaft rotation.
.
Step 46.
Put cab FOAM SYSTEM switch to off position (WP 0004) and release.
Remove pump
house panel K (WP 0339).
While an assistant puts cab or pump operator’s panel
FOAM SYSTEM switch to ON position (WP 0004), check if eductor valve operates to
open position.
.
If eductor valve does not operate to open position, go to Step 51.
.
Step 47.
Put cab or pump operator’s panel FOAM SYSTEM switch to OFF position (WP 0004)
and release.
Check if air lines from air control valve manifold to foam system shutoff
valve are free from kinks and damage.
.
If air lines are kinked or damaged, replace damaged air lines (WP 0374).
.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION